Permit Information
Permit NumberFIR14-00518
StatusFinaled
Name TASKER ELECTRICAL CONSTRUCTION INC
Site Address 8455 W WESTPARK ST
Project Name8455 Westpark East Warehouse
Customer Number 
ePlanReviewNo
Description
This parcel is being separated into two parcels, thus requiring separate fire alarm systems. Existing panel is to be removed and two new systems will be installed under separate permits. (FIR14-00517 and FIR14-00518) Fire alarm panel replacement is for sprinkler monitoring of Vanilla Finish warehouse. Associated with building permit BLD14-02274.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/14/20161/15/20161/15/2016APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/13/20161/14/20161/14/2016PFAIL
DetailsTroy Cobbley
Need the as-built drawings as discussed and then the project can be finaled.
Telephone call  1/6/2016 DONE
Scott Arrelano received a call from the property manager indicating roof top units 14 and 15 will be decommissioned from use. Both units are to have electrical and gas connections removed and locked out from further use. They are to be abandonded in place due to prohibitive cost of removing them.
Miscellaneous action  1/6/2016 DONE
Marv Meyer of Russell Corp. sent a pdf file that shows all rooftop HVAC equipment locations including units 10 and 14 that are being decommissioned. The drawing has been uploaded into documents.
INSP-Final Inspection2/5/20152/6/20152/6/2015AFAIL
DetailsTroy Cobbley
Fire alarm testing complete. Need the non-functional hvac units repaired or removed. If repaired I need to finish testing. If removed I need revised drawings.
Permit Ready to Issue  2/2/2015 DONE
Issue and Print Permit  2/2/2015 DONE
Inspection Record Card- Fire2/2/2015 2/2/2015 DONE
DetailsBrittany Hill
INSP-Final Inspection1/29/20151/30/20151/30/2015AFAIL
DetailsTroy Cobbley
Need plan modificatios and the hvac unit/shut down addressed.
Alarm Plan Check1/30/2015 1/30/2015 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  1/30/2015 DONE
Plan modification allprved with drawing notation and review comments. Taken to front desk for processing.
Inspection Record Card- Fire1/30/2015 1/30/2015 DONE
DetailsBrittany Hill
INSP-Final Inspection1/29/20151/29/20151/29/2015AFAIL
DetailsTroy Cobbley
We were only able to test one duct smoke detector due to not being able to get the remaining hvac units to function. I noted that the smoke detectors for the fire door release do not appear to be installed per NFPA 80 and Chapter 17 of NFPA 72
INSP-Final Inspection1/29/20151/30/20151/29/2015ACANC
DetailsTroy Cobbley
Please notify Greg 30 min. prior to arrival. Thank you! Phone #: ###-#### >> Inspection requested via web by Stacie Tasker Inspection cancelled from web by: Stacie Tasker
Plan resubmittals received  1/29/2015 DONE
Two copies of Application/booklet, FA00 and FA2.0
INSP-Final Inspection1/27/20151/28/20151/28/2015AFAIL
DetailsTroy Cobbley
Resubmit plans for a "plan modification" for the additional flow switches, tamper switches and the cellular dialer. Provide auto-resetting tamper switches on the existing anti-freeze loop control valves, repair or remove the non-functional hvac units to facilitate the testing of the duct smoke detectors, remove or provide connection to the door mags.
Issue and Print Permit  11/13/2014 DONE
Telephone call  11/4/2014  
DetailsCandy A. Nichols
called Greg tof let know plan mods plans are ready and how much is owed. Left message on his machine
Inspection Record Card- Fire11/4/2014 11/4/2014 DONE
DetailsCandy A. Nichols
Plan assigned to (Lee)10/31/2014 11/3/2014 DONE
DetailsLee G Meredith
Alarm Plan Check11/3/2014 11/3/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  11/3/2014 DONE
Plans approved with review comments. taken to front desk for processing.
Plan resubmittals received  10/31/2014 DONE
DetailsChristina Prado
**PLAN MOD** received two sets of revised apps, plans and submittal packet;Plans taken to Lee for further review
INSP-Final Inspection8/8/20148/8/20148/8/2014PFAIL
DetailsTroy Cobbley
Provide city approved data sheets and as-builts/submittals as discussed. Functional testing of system passed.
CHANGE STATUS TO (ISS)  8/8/2014 DONE
Plan assigned to (Lee)7/21/2014 7/28/2014 DONE
DetailsLee G Meredith
1st review completed  7/28/2014 PASS
Alarm Plan Check7/28/2014 7/28/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  7/28/2014 DONE
Review passed. As built floor plans with calculations to be provided at acceptance test. Documents taken to front desk for processing.
Telephone call  7/28/2014 DONE
DetailsChristina Prado
Called Greg to advise permit is ready for pick up and gave fees due
Permit Ready to Issue  7/28/2014 DONE
DetailsChristina Prado
Inspection Record Card- Fire7/28/2014 7/28/2014 DONE
DetailsChristina Prado
Telephone call  7/22/2014 DONE
Mary Froemke call to say that the perminant power for this site (BLD14-01680) was being removed and temporary power was being supplied until the demo work was finished and the existing building was seperated into 2 buildings. Because of this, the existing fire alarm system will need to be repaced and 2 systems installed. To keep sprinkler monitoring intact, new panels will be installed. A plan modification will be submitted with floor plans showing vanilla finish sprinkler montioring. I informed her that this was acceptable to keep the systems properly monitored but systems will need to have all required detection and off site monitoring installed ASAP to insure constant monitoring. (Also see FIR14-00517)
Application received  7/21/2014