INSP-Final Inspection | 10/26/2015 | 10/27/2015 | 10/27/2015 | A | PASS |
Jim Page
|
|
|
Final fire sprinkler inspcetion passed/complete
|
INSP-Final Inspection | 10/27/2014 | 10/28/2014 | 10/28/2014 | A | FAIL |
Troy Cobbley
|
|
|
Pendant sprinkler coverage is blocked by new soffit/shelf.
|
INSP-Sprinkler Rough-in | 9/2/2014 | 9/2/2014 | 9/2/2014 | P | PASS |
Troy Cobbley
|
|
|
Branchlines, hangers and drops ok. Will need another rough-in inspection prior to cover once the pendants are actually placed. Possible corrections needed for upright coverage outside of the new space at the roof deck
|
Permit Ready to Issue | | | 8/19/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Issue and Print Permit | | | 8/19/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 8/19/2014 | | 8/19/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Plan assigned to (Tim) | 7/30/2014 | | 7/30/2014 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 7/30/2014 | | 7/30/2014 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
1st review completed | | | 7/30/2014 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/30/2014 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 7/22/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 22 2014 10:01AM
|