INSP-Final Inspection | 12/11/2014 | 12/12/2014 | 12/12/2014 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 12/9/2014 | 12/9/2014 | 12/9/2014 | P | FAIL |
Troy Cobbley
|
|
|
Could not final out inspection due to fire alarm problems. However the forward flush passed
|
INSP-Final Inspection | 12/5/2014 | 12/5/2014 | 12/5/2014 | P | CANC |
Troy Cobbley
|
|
|
Canceled per discussion with Jeff Packham
|
INSP-Sprinkler Rough-in | 10/24/2014 | 10/24/2014 | 10/24/2014 | P | PASS |
Troy Cobbley
|
|
|
The north and south stairwell insulation is complete and can be covered. The second floor insulation is complete and piping can be covered.
|
INSP-Sprinkler Rough-in/Hydro | 10/14/2014 | 10/14/2014 | 10/14/2014 | P | PASS |
Troy Cobbley
|
|
|
2nd & 3rd floor overhead hydro tests passed
|
INSP-Sprinkler Rough-in/Hydro | 10/9/2014 | 10/10/2014 | 10/10/2014 | A | PASS |
Troy Cobbley
|
|
|
1st floor hydro test passed on the second try.
|
INSP-Sprinkler Rough-in | 10/8/2014 | 10/9/2014 | 10/9/2014 | A | PART |
Troy Cobbley
|
|
|
Todays inspection was for a rough-in for the second and third floors. Rough-in passed. Two locations are marked where heads have not been installed yet. Third floor piping is ok to cover. First, second and the stairwells can not be covered until insulation/filling has been verified.
|
INSP-Sprinkler Rough-in | 9/10/2014 | 9/11/2014 | 9/11/2014 | A | PASS |
Troy Cobbley
|
|
|
Inspection was for the first floor only. With the removal of the upright heads the installation matches the revised plans. Tim is ok with the revised piping in the first floor. Piping can not be covered until the installation of the insulation has been approved.
|
Miscellaneous action | | | 9/11/2014 | | PASS |
|
|
|
Remote area changed slightly during installation. The hydraulic calculations are OK.
|
Sprinkler Plan Check | 9/10/2014 | | 9/10/2014 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/10/2014 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 9/10/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Issue and Print Permit | | | 9/10/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 9/10/2014 | | 9/10/2014 | | DONE |
Candy A. Nichols
|
|
|
|
INSP-Sprinkler Rough-in | 8/28/2014 | 8/29/2014 | 8/29/2014 | A | PART |
Troy Cobbley
|
|
|
Inspection turned into a conference. I noted, and we discussed, the extensive amount of obstructions caused by mechanical duct work. It does not appear that any of the obstruction rules for the CC heads can be met and that additional sprinkler heads will be required. With additional heads hydraulic calculations/pipe routing will/could be effected and plan modifications required. I also noted that the area under the stairs is combustible and does not have sprinkler protection. This will require special consideration to meet NFPA 13 requirements prior to a cover inspection.
|
Sprinkler Plan Check | 8/18/2014 | | 8/18/2014 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
1st review completed | | | 8/18/2014 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/18/2014 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 8/18/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Issue and Print Permit | | | 8/18/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 8/18/2014 | | 8/18/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 8/18/2014 | | 8/18/2014 | | DONE |
Candy A. Nichols
|
|
|
|
(F) Reprint permit | | | 8/18/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 8/18/2014 | | 8/18/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Plan assigned to (Tim) | 8/15/2014 | | 8/15/2014 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 8/13/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 13 2014 9:27AM
|