INSP-Final Inspection | 10/13/2014 | 10/14/2014 | 10/14/2014 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Elevator still does not recall correctly. Per scott and I's conversation and a signed letter from Gary Barnes with the state of Idaho a final is ok.
|
INSP-Final Inspection | 10/10/2014 | 10/13/2014 | 10/13/2014 | A | FAIL |
Troy Cobbley
|
|
|
Same issues as previously noted
|
Miscellaneous action | | | 10/2/2014 | | DONE |
|
|
|
As built drawings received.
|
INSP-Final Inspection | 10/1/2014 | 10/1/2014 | 10/1/2014 | P | FAIL |
Forrest France
|
|
|
Items noted include; missing SD at the new nac panel, elevator recall is malfunctional, audible notification to meet temporal pattern- refer to plan review comment #7.
|
Permit Ready to Issue | | | 9/2/2014 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/2/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/2/2014 | | 9/2/2014 | | DONE |
Kristal Soland
|
|
|
|
Alarm Plan Check | 8/29/2014 | | 8/29/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 8/29/2014 | | DONE |
|
|
|
Plans approved with comments and notation. Projectdox updated.
|
Plan resubmittals received | | | 8/28/2014 | | DONE |
|
|
|
|
Telephone call | | | 8/14/2014 | | DONE |
|
|
|
Charly Bayne called to discuss deficiencies. I informe him tha notification was lacking an that existing equipment was not clearly identified. I let him know that I would be returning them for corrections.
|
1st review completed | | | 8/14/2014 | | FAIL |
|
|
|
See review comments.
|
Miscellaneous action | | | 8/14/2014 | | DONE |
|
|
|
Emailed review comments to Charlie Bayne
|
Application received | | | 8/13/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 13 2014 10:56AM
|
Plan assigned to (Lee) | 8/13/2014 | | 8/13/2014 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 8/13/2014 | | DONE |
|
|
|
Via email, I requested some clarification. The drawings do not clearly indicate existing and new devices. Dante's autoresponse indicated he was on vacation until 8/28. I called Charlie Bayne and left a message for him to call me for further discussion.
|