Miscellaneous action | | | 9/2/2015 | | DONE |
|
|
|
Heat tracing is no longer required per project HVAC contractor. See letter located in ProjectDOX document folder and revised drawing FP-3
|
INSP-Final Inspection | 7/26/2015 | 7/27/2015 | 7/27/2015 | A | PASS |
Jim Page
|
|
|
Previously noted items corrected, Dry pendant escutcheons on order, will be installed when received, fire sprinkler inspection passed/complete
|
INSP-Final Inspection | 7/23/2015 | 7/24/2015 | 7/24/2015 | A | PART |
Jim Page
|
|
|
Trip test of the dry pipe valve, including the new accelerator - tested OK within 45 seconds. Escutcheons missing on multiple heads in parking area, need to have air maintenance installed on air line supply to dry system, compressor provided regulator not approved for air maintenance.
|
INSP-Final Inspection | 7/20/2015 | 7/20/2015 | 7/20/2015 | P | FAIL |
Thomas Walsh
|
|
|
Trip test of dry pipe valve protecting perking garage. Trip test resulted in 90 seconds to delivery of water to IT. Contractro agreed to install an accelerator to get within 60 seconds timeframe. All other tests, including low-air, tampers, ext. bell, etc., tested OK
|
INSP-Sprinkler Rough-in/Hydro | 7/16/2015 | 7/16/2015 | 7/16/2015 | P | PASS |
Thomas Walsh
|
|
|
Hydrotest (200 psi @ 2hrs.) of dry pipe system protecting parking garage level. PASSED
|
Sprinkler Plan Check | 9/4/2014 | | 9/4/2014 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
1st review completed | | | 9/4/2014 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/4/2014 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 9/4/2014 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/4/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/4/2014 | | 9/4/2014 | | DONE |
Kristal Soland
|
|
|
|
Plan assigned to (Tim) | 9/3/2014 | | 9/3/2014 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 8/25/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 25 2014 4:29PM
|