Case Summary | | | 2/3/2015 | | |
|
|
|
|
INSP-Final Inspection | 9/24/2014 | 9/25/2014 | 9/25/2014 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Miscellaneous action | | | 9/24/2014 | | DONE |
|
|
|
Paula O'Meara emailed as built drawings. They have been imported into documents in Tidemark.
|
INSP-Final Inspection | 9/16/2014 | 9/18/2014 | 9/18/2014 | P | FAIL |
Troy Cobbley
|
|
|
The north and south duct smoke detectors did not shut down the hvac units immediately as required per IMC 606.2.1. Since the units are less than 2,000cfm I gave Dutch the option of either fixing the shutdown or remove them all together and providing as-builts. The center duct detector and the Ansul hood did test ok.
|
Issue and Print Permit | | | 8/28/2014 | | DONE |
Tisha Gallop
|
|
|
|
Application received | | | 8/27/2014 | | |
|
|
|
|
Plan assigned to (Lee) | 8/27/2014 | | 8/27/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 8/27/2014 | | DONE |
|
|
|
|
Alarm Plan Check | 8/27/2014 | | 8/27/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 8/27/2014 | | DONE |
|
|
|
Quick permit plans approved without review comments. Plans taken to front desk for processing.
|
Telephone call | | | 8/27/2014 | | DONE |
Candy A. Nichols
|
|
|
Called Paula to let know permit is ready and how much is owed
|
Permit Ready to Issue | | | 8/27/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 8/27/2014 | | 8/27/2014 | | DONE |
Candy A. Nichols
|
|
|
|