INSP-Final Inspection | 11/25/2014 | 11/26/2014 | 12/1/2014 | P | PASS |
Forrest France
|
|
|
Verified previous correction items for completion. Fire alarm permit finaled.
|
CHANGE STATUS TO (ISS) | | | 11/25/2014 | | DONE |
Christina Prado
|
|
|
|
Plan resubmittals received | | | 11/21/2014 | | DONE |
|
|
|
|
Alarm Plan Check | 11/21/2014 | | 11/21/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/21/2014 | | DONE |
|
|
|
Resubmittal approved. No new review comments written. Projectdox updated.
|
INSP-Final Inspection | 11/19/2014 | 11/20/2014 | 11/20/2014 | A | FAIL |
Troy Cobbley
|
|
|
The new horns in the remodeled area do not sync with the existing horns in the other areas. Also there are exiting smoke detectors, which are over spaced, that are not shown on the city approved plans. A/v's tested ok with the activation of one of the existing smoke detectors. New NAC panel is supervised by the FACP.
|
Plan assigned to (Lee) | 9/15/2014 | | 9/15/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 9/15/2014 | | PASS |
|
|
|
|
Alarm Plan Check | 9/15/2014 | | 9/15/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 9/15/2014 | | DONE |
|
|
|
Plans approved woth review comments and notation on drawings. Projectdox updated.
|
Permit Ready to Issue | | | 9/15/2014 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/15/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/15/2014 | | 9/15/2014 | | DONE |
Tisha Gallop
|
|
|
|
Application received | | | 9/12/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 12 2014 2:10PM
|