INSP-Final Inspection | 9/23/2015 | 9/24/2015 | 9/23/2015 | A | PASS |
Thomas Walsh
|
|
|
Test of fire alarm system interface with egress hardware (mag locks) to ensure proper functioning - PASSED. NOTE: Fire alarm system testing passed final inspection. As this is a network system, the new address for this building will have to be upgraded to ensure that emergency crews get the correct information from dispatch.
|
INSP-Final Inspection | 9/15/2015 | 9/21/2015 | 9/21/2015 | P | PART |
Thomas Walsh
|
|
|
Fire alarm test of all fire sprinkler and hood and duct FP systems interface, SDs, MPs, HVAC DDs, SFDs, notification devices, etc. All tested OK. NOTE: FA interface to egress door hardware (mag. locks) not tested - not ready.
|
CHANGE STATUS TO (ISS) | | | 12/4/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Alarm Plan Check | 12/3/2014 | | 12/3/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 12/3/2014 | | DONE |
|
|
|
Resubmittal approved with review comments. Projectdox updated.
|
Miscellaneous action | | | 12/1/2014 | | DONE |
|
|
|
Dante emailed to indicate that they will be changing this building design to use chime strobes instead of horn strobes. He requested the project be opened for upload of the revised submittal.
|
Plan resubmittals received | | | 12/1/2014 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/25/2014 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/25/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/25/2014 | | 11/25/2014 | | DONE |
Christina Prado
|
|
|
|
Alarm Plan Check | 11/21/2014 | | 11/21/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/21/2014 | | DONE |
|
|
|
Plans approved with review comments. Projectdox updated.
|
Plan resubmittals received | | | 11/20/2014 | | DONE |
|
|
|
|
Telephone call | | | 10/31/2014 | | DONE |
|
|
|
Teleconfirence with Ron Hill, Romeo Gervais and Lee meredith with Bill Boehler and Anthony Luciano of AG Architects. Discussion covered audible and visual notification requirements and expectations for the skilled nuring cottages and memory support wing. PDS is requiring visual notification per NFPA 72 requirements for public or private mode. AG wants to have a modified private mode. Discussions are to continue after AG sends nurses paging system product documentation.
|
Plan assigned to (Lee) | 10/1/2014 | | 10/1/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 10/1/2014 | | FAIL |
|
|
|
See 1st alarm review comments.
|
Miscellaneous action | | | 10/1/2014 | | DONE |
|
|
|
Emailed failed review comments to applicant.
|
Application received | | | 9/29/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 29 2014 4:13PM
|