Permit Information
Permit NumberFIR14-00718
StatusFinaled
Name WEBSTER FIRE PROTECTION
Site Address 1124 S ROOSEVELT ST
Project NameRed Rock Church Addition/Remod
Customer Number 
ePlanReviewYes
Description
Add new fire alarm system to existing building. Associated with building permit BLD14-00562.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/3/201412/3/201412/3/2014PPASS
DetailsForrest France
Verified C/N items, as-built plans accepted. Points map and record of completion documents to be provided as agreed.
INSP-Alarm Testing12/1/201412/2/201412/2/2014APART
DetailsForrest France
Functional testing and inspection of the new fire alarm system completed. Items needed prior to final include as-built drawings reflecting field modifications to show four added strobes, deleted kitchen hood monitor, revised cd settings at the multi-purpose rooms and west corridor, riser points added for dry system pressure switches. Need to add notification at the kitchen area restroom. Post signage at the door to the FACP room.
Permit Ready to Issue  10/30/2014 DONE
Issue and Print Permit  10/30/2014 DONE
Inspection Record Card- Fire10/30/2014 10/30/2014 DONE
DetailsChristina Prado
Plan assigned to (Lee)10/29/2014 10/29/2014 DONE
DetailsLee G Meredith
Miscellaneous action  10/29/2014 DONE
Plans uploade to projectdox on 10-24-14
1st review completed  10/29/2014 PASS
Alarm Plan Check10/29/2014 10/29/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/29/2014 DONE
Plans approved with review comments and conditions. Projectdox updated.
Telephone call  10/1/2014 DONE
Ken Webster call to inform me that although he has submitted his application and documents, He does not have a returned set from the engineer of record. Once he has received this, he will submit it and complete the upload process to start the work flow. He did not have an estimate on when this would be done so there may be an extended delay before plan review can be completed.
Telephone call  10/1/2014 DONE
Ken Webster call to indicate that duct smoke detectors are required, in his opinion but they are not shown on the drawings. The engineer of record feels that they are not requires and stated this in an RFI response to Ken.
Application received  9/30/2014 DONE
Application submitted via PDS Online on Sep 30 2014 10:16AM