INSP-Final Inspection | 11/10/2015 | 11/10/2015 | 11/10/2015 | P | PASS |
Jim Page
|
|
|
Final fire alarm passed/complete per activities entered by Tom Walsh on 29OCT2015.
|
INSP-Final Inspection | 10/29/2015 | 10/29/2015 | 10/29/2015 | P | PASS |
Thomas Walsh
|
|
|
Fire alarm system test of wings F & G, including all unit SDs. corridor SDs, manual pulls, notification devices (audibility), FSDs, elevator recall functions, etc. All tested OK. Two unit SDs had to be reprogrammed to activate correctly. NOTE: All fire sprinkler system testing completed with wing F &G.
|
INSP-Final Inspection | 10/21/2015 | 10/26/2015 | 10/26/2015 | A | PART |
Thomas Walsh
|
|
|
Fire alarm system test for parking garage #2, which is under wings EF&G.=, including manual pulls, elevator recall and shunt trip functions, and audio/visual notification devices - all tested OK
|
Alarm Plan Check | 10/14/2014 | | 10/14/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 10/14/2014 | | DONE |
|
|
|
Plans approved with review comments and conditions. Projectdox updated.
|
Permit Ready to Issue | | | 10/14/2014 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/14/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/14/2014 | | 10/14/2014 | | DONE |
Kristal Soland
|
|
|
|
Plan assigned to (Lee) | 10/13/2014 | | 10/13/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 10/13/2014 | | PASS |
|
|
|
|
Application received | | | 10/2/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Oct 2 2014 2:16PM
|