INSP-Final Inspection | 6/22/2015 | 6/22/2015 | 6/22/2015 | P | PASS |
Thomas Walsh
|
|
|
Final Inspection - PASSED
|
INSP-Sprinkler Rough-in/Hydro | 6/22/2015 | 6/22/2015 | 6/22/2015 | P | PASS |
Thomas Walsh
|
|
|
Retested one HVAC unit for SD shutdown for the Bldg. D commons area. The unit shutdown when tested. That was the last test needed for final sign-off. PASSED and Finaled.
|
INSP-Final Inspection | 6/12/2015 | 6/12/2015 | 6/12/2015 | A | FAIL |
Thomas Walsh
|
|
|
Final inspection of fire alarm system for Bldg D and common areas. One HVAC duct detector is not shutting down its assoc, HVAC unit. Three other units tested OK.
|
INSP-Alarm Testing | 6/9/2015 | 6/10/2015 | 6/10/2015 | P | PART |
Thomas Walsh
|
|
|
Fire alarm system testing for Bldg. D commons area, including MP, SDs, CO detectors, heat detectors. One H/S unit in the kitchen area is not silencing properly. No FSDs. or elevators tested this visit.
|
INSP-Alarm Testing | 6/8/2015 | 6/8/2015 | 6/8/2015 | P | PART |
Thomas Walsh
|
|
|
Inspection/ test of fire alarm system for the permit coverage area, except common area of Bldg D., including manual pulls, smoke detection, waterflows, tamper supervisories, and audibility/visual device testing. All addresses appeared to be accurate. NOTE: No FSDs or elevator functions tested this visit.
|
Permit Ready to Issue | | | 11/25/2014 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/25/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/25/2014 | | 11/25/2014 | | DONE |
Christina Prado
|
|
|
|
Alarm Plan Check | 11/24/2014 | | 11/24/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/24/2014 | | DONE |
|
|
|
Resubmittal approved with review comments. Projectdox updated.
|
Plan resubmittals received | | | 11/20/2014 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 10/14/2014 | | 10/14/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 10/14/2014 | | FAIL |
|
|
|
See 1st review comments.
|
Miscellaneous action | | | 10/14/2014 | | DONE |
|
|
|
Emailed review comments to applicant.
|
Application received | | | 10/3/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Oct 3 2014 10:53AM
|