Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberFIR14-00745
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 222 S AUTO DR
Project NameLARRY H MILLER COLL. REP. CNTR
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of a one new dry and one new wet system to protect a new addition. The dry system is protecting a drive in canopy. The wet system protects the remainder of the new addition. The 6” underground supplies a 6” backflow preventer, 6” wet system riser and 3” wet system riser.

The underground is under permit FIR14-00596

Per the designer there is no flammable liquid spraying in the permitted scope of work. There is a large opening adjoining the paint department expansion. The designer indicated there was no flammable liquid spraying in this adjoining area.

Larry H. Miller - Body Shop and Office Addition - To demolish and remove an approximate 7,000 sq. ft., two story office area on the northeast corner of the building and construct a 21,035 sq. ft. office and repair garage addition, with a 2,035 sq. ft. storage mezzanine on the north end of an existing auto collision repair building. The existing showroom and repair shop on the south are unchanged and are separated from the north portion of the building by a four-hour firewall. This permit also includes related site improvements. This building is fully fire sprinklered. The sprinklers are used for area increase. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/29/20151/30/20151/30/2015APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/28/20151/29/20151/29/2015AFAIL
DetailsTroy Cobbley
Outside alarm bell did not ring upon activation of the dry pipe system.
INSP-Sprinkler Rough-in/Hydro1/20/20151/21/20151/21/2015PPASS
DetailsTroy Cobbley
24 hr air test passed
INSP-Sprinkler Rough-in/Hydro1/20/20151/20/20151/20/2015PPART
DetailsTroy Cobbley
Rick-24 hr air test started at 10:00am with 40 psi on the guage
INSP-Sprinkler Rough-in/Hydro1/15/20151/16/20151/16/2015APASS
DetailsTroy Cobbley
Overhead 200lb hydro for both the wet and dry systems passed.
INSP-Sprinkler Rough-in1/14/20151/15/20151/15/2015APASS
DetailsTroy Cobbley
Piping in office area can be covered. 6" main installed and passed. Heads under doors installed and passed
INSP-Sprinkler Rough-in12/29/201412/30/201412/30/2014APASS
DetailsTroy Cobbley
6" main needs to be installed/inspected and the tie-in's to the existing system. Outside canopy is ok to cover. Need sprinkler coverage installed under doors.
Sprinkler Plan Check12/22/2014 12/22/2014 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  12/22/2014 DONE
DetailsTim Frost
Permit Ready to Issue  12/22/2014 DONE
Issue and Print Permit  12/22/2014 DONE
DetailsCandy A. Nichols
Inspection Record Card- Fire12/22/2014 12/22/2014 DONE
DetailsCandy A. Nichols
INSP-Sprinkler Rough-in12/19/201412/19/201412/19/2014PPASS
DetailsTroy Cobbley
Sprinkler piping above the restrooms is ok to cover.
INSP-Sprinkler Rough-in10/29/201410/29/201410/29/2014PPASS
DetailsTroy Cobbley
The 5'-0" stub out is ok to bury.
(F) Reprint permit  10/16/2014 DONE
DetailsCandy A. Nichols
Inspection Record Card- Fire10/16/2014 10/16/2014 DONE
DetailsCandy A. Nichols
Miscellaneous action  10/15/2014 DONE
Requested additional information via email

Do you have the existing hydraulic calculations?
What was the original flow test information?
Did the existing riser have a backflow preventer?
Can you email a set of the existing drawings and calculations?
Is there an additional lead in?
How many square foot is in this system including the existing and new?

I am concerned if the existing system will still function properly hydraulically.

In addition, if this is all one system, it may well be over 52k sqft.
Sprinkler Plan Check10/15/2014 10/15/2014 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  10/15/2014 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  10/15/2014 DONE
DetailsTim Frost
Permit Ready to Issue  10/15/2014 DONE
DetailsCandy A. Nichols
Issue and Print Permit  10/15/2014 DONE
DetailsCandy A. Nichols
Inspection Record Card- Fire10/15/2014 10/15/2014 DONE
DetailsCandy A. Nichols
Plan assigned to (Tim)10/14/2014 10/14/2014 DONE
DetailsTim Frost
Intake Approval  10/14/2014 PASS
Miscellaneous action  10/14/2014 DONE
Email for more information.

Hello Nathan,

I have a few general questions is regards to this project. Please, respond back in email.

1. What exactly is being done in the Paint Department Expansion?
2. I notice there is a large opening into the existing building from the Paint Department Expansion. Does this opening have a fire door?
3. What exactly is being done on the adjacent/existing side of the opening?
4. Is there a spray paint booth in the current project area?
5. Is there any flammable liquid spraying in the project area? If so where exactly?

Miscellaneous action  10/14/2014 DONE
Response from email

Tim,

Please see below answers in red. Let me know if you have any other questions.

Thanks,

Nathan Stenquist
Project Design
Treasure Valley Fire Protection

I have a few general questions is regards to this project. Please, respond back in email.

1. What exactly is being done in the Paint Department Expansion? The dealership will use this are to prep vehicles for paint (i.e. wash and stage).
2. I notice there is a large opening into the existing building from the Paint Department Expansion. Does this opening have a fire door? There will be no fire door.
3. What exactly is being done on the adjacent/existing side of the opening? Currently the existing area is being used for the same type of prep and the only painting is done in the paint booth in the SE corner of the building.
4. Is there a spray paint booth in the current project area? There will be no paint booth in the new project area.
5. Is there any flammable liquid spraying in the project area? If so where exactly? There will be no flammable liquid spraying in the new project area. The only spraying will be in the existing paint booth that was previously properly protected and not in our current scope.


Cordially,

Tim Frost, S.E.T.
Fire Sprinkler Plans Examiner
Fire Code Plans Examiner
Application received  10/13/2014 DONE
Application submitted via PDS Online on Oct 13 2014 10:39AM