INSP-Final Inspection | 8/19/2015 | 8/20/2015 | 8/20/2015 | A | PASS |
Jim Page
|
|
|
Final inspection passed/complete
|
CHANGE STATUS TO (ISS) | | | 8/19/2015 | | DONE |
|
|
|
|
INSP-Final Inspection | 6/11/2015 | 6/11/2015 | 6/11/2015 | P | FAIL |
Jim Page
|
|
|
This is not a final inspection, this was an underground cover inspection (Pot Marked Inspection for proper cover depth) and an underground flush. Pipe is at an approved depth and supply line is flushed/complete
|
INSP-Conference | 6/10/2015 | 6/11/2015 | 6/11/2015 | A | DONE |
Jim Page
|
|
|
Verfied with on site contact, "pot marks" are being provided to verify underground piping cover.
|
INSP-Final Inspection | 5/12/2015 | 5/18/2015 | 5/18/2015 | A | FAIL |
Troy Cobbley
|
|
|
No head located over riser in riser room.
Fire bell not located on street side of building, bell also needs sticker installed
No record of underground being approved for cover.
No record of underground flush witness.
No backflow preventer installed on fire riser.
CPVC riser mounted to far from wall.
|
INSP-Sprinkler Rough-in | 2/11/2015 | 2/11/2015 | 2/11/2015 | P | PART |
Forrest France
|
|
|
Overhead work approved for cover, tenting and insulation install verified.
|
INSP-Sprinkler Rough-in | 2/3/2015 | 2/3/2015 | 2/3/2015 | P | PART |
Forrest France
|
|
|
Verified stamped plans on site, completed overhead rough-in inspection. * NOTE: Need to verify tenting insulation prior to cover. No record to date of an UG fire supply line inspection prior to bury.
|
INSP-Sprinkler Rough-in | 1/30/2015 | 2/2/2015 | 2/2/2015 | A | NR |
Forrest France
|
|
|
Missing approved plans on site. Need to verify cold cavity protection at riser transitions to upper ceiling levels.
|
Permit Ready to Issue | | | 12/23/2014 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/23/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/23/2014 | | 12/23/2014 | | DONE |
Kristal Soland
|
|
|
|
Sprinkler Plan Check | 12/22/2014 | | 12/22/2014 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/22/2014 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 11/4/2014 | | 11/4/2014 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 11/4/2014 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 11/4/2014 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Plan assigned to (Tim) | 11/3/2014 | | 11/3/2014 | | DONE |
Tim Frost
|
|
|
|
Intake Approval | | | 11/3/2014 | | PASS |
|
|
|
|
Application received | | | 10/30/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Oct 30 2014 8:06AM
|