Permit Information
Permit NumberFIR14-00837
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 701 E MORRISON KNUDSEN PLAZA DR Unit: 101
Project NameWGI Plaza II Elevator upgrade
Customer Number 
ePlanReviewYes
Description
Adding Smoke detectors in basement and first and third floor elevator lobbies (Second and fourth floor lobbies have existing smoke detectors). There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/6/20158/6/20158/6/2015PPASS
DetailsJim Page
Previously noted items corrected, fire alarm inspection passed/complete
INSP-Final Inspection3/24/20153/26/20153/26/2015AFAIL
DetailsForrest France
Need to relocate the SD at the 3rd floor elevator lobby a min. of 3' from the HVAC diffuser, basement elevator lobby SD needs mounted at the deck. 1st floor lobby and machine room smokes tested okay.
Plan resubmittals received  11/17/2014 DONE
Alarm Plan Check11/17/2014 11/17/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  11/17/2014 DONE
Plans approved with review comments. Projectdox updated.
Permit Ready to Issue  11/17/2014 DONE
Issue and Print Permit  11/17/2014 DONE
Inspection Record Card- Fire11/17/2014 11/17/2014 DONE
DetailsChristina Prado
Application received  11/13/2014 DONE
Application submitted via PDS Online on Nov 13 2014 10:54AM
Plan assigned to (Lee)11/13/2014 11/13/2014 DONE
DetailsLee G Meredith
1st review completed  11/13/2014 FAIL
Failed pre-screen review. Applicant notified via email.