INSP-Final Inspection | 8/6/2015 | 8/6/2015 | 8/6/2015 | P | PASS |
Jim Page
|
|
|
Previously noted items corrected, fire alarm inspection passed/complete
|
INSP-Final Inspection | 3/24/2015 | 3/26/2015 | 3/26/2015 | A | FAIL |
Forrest France
|
|
|
Need to relocate the SD at the 3rd floor elevator lobby a min. of 3' from the HVAC diffuser, basement elevator lobby SD needs mounted at the deck. 1st floor lobby and machine room smokes tested okay.
|
Plan resubmittals received | | | 11/17/2014 | | DONE |
|
|
|
|
Alarm Plan Check | 11/17/2014 | | 11/17/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/17/2014 | | DONE |
|
|
|
Plans approved with review comments. Projectdox updated.
|
Permit Ready to Issue | | | 11/17/2014 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/17/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/17/2014 | | 11/17/2014 | | DONE |
Christina Prado
|
|
|
|
Application received | | | 11/13/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Nov 13 2014 10:54AM
|
Plan assigned to (Lee) | 11/13/2014 | | 11/13/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 11/13/2014 | | FAIL |
|
|
|
Failed pre-screen review. Applicant notified via email.
|