Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR14-00839
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1600 W GOWEN RD
Project NameSKYWEST MAINTENANCE HANGAR
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of a new 132,770 building. Group I hangar, office and warehouse space. All to be fully protected by 189,000 gallon NFPA 22 water storage tank, two 3000 Gpm @150 psi diesel fire pumps in parallel and one back up 3000 Gpm @150 psi electric fire pump. There will be three wet systems, three 2% high expansion foam generator systems, and one 3% AFFF hose system..

The hangar is protected with an automatic sprinkler system and a 2% low level high expansion foam system with AFFF hose stations. The high expansion foam is based on local application for duration of 12 minutes

NOTE: The type of high piled storage in the parts area is not defined. The system is therefore, designed based on BMC 7-01-53. Before any actual occupancy or storage can take place, a resubmittal is required describing the actual type of storage and storage configuration.

The underground is under permit FIR14-00783

(SKYWEST MAINTENANCE HANGAR – Cold Shell Permit) This permit is to construct the exterior shell and associated foundation to a new 132,770 square feet Maintenance Hangar. Grading, drainage and Utilities approved under BLD14-02396. All work per approved plans and attached engineering. Scope of work includes: construction of new foundation, construction of pre-manufactured steel building, exterior doors, exterior windows, one-hour fire separation between hangar and future office/assembly/work area, all exterior envelope compliance, installation of new loading dock and equipment, and exterior finishes.

At this time the TI has not been submitted
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/20/20158/21/20158/21/2015APASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Final Inspection8/14/20158/14/20158/14/2015PCANC
DetailsJim Page
Spoke with POC over the phone, Mike Phone #: ###-####, Simplex still needs to install pull stations for foam system avtivation, cannot final until pulls stations are installed and tested for actuation.
INSP-Sprinkler Rough-in8/12/20158/12/20158/12/2015PPASS
DetailsTroy Cobbley
Todays inspection was for flow verification of the foam system. This verification failed. See the plan reviewer attached notes on the specificsof what was witnessed

______________________________________
Below add by Plan Reviewer TRF

Based on the following the foam test PASSED.

NFPA 409 6.1.1 (3)
NFPA 409 6.2.5.3 (withing 5' in 3 minutes)
NFPA 409 6.2.5.5.1 (local application, NFPA 11)
NFPA 11 6.13.3.3.1 (2 ft within 2 min)
The requiment of 2' of foam was met in 1:50 seconds.



INSP-Sprinkler Rough-in8/11/20158/11/20158/11/2015PDONE
DetailsTroy Cobbley
Boise Fire Dept. witnessed the flowing water at the foam generators. Forrest France verified required pressure at foam generator.
INSP-Sprinkler Rough-in/Hydro8/6/20158/7/20158/7/2015APASS
DetailsTroy Cobbley
Overhead hydro tests of the four foam systems (DDX valves) passed.
INSP-Supply line flush8/5/20158/6/20158/6/2015ACANC
DetailsTroy Cobbley
Mike Phone #: ###-####
INSP-Conference8/4/20158/5/20158/5/2015ADONE
DetailsTroy Cobbley
Todays inspection was for certification of the 3 fire pumps. Inspection passed. We found that all three pumps are 3psi to 7psi above on Churn. Both diesel pumps are 4psi to 5psi low at 150%. After conferencing with Tim Frost and Gary with Tolco pumps that this is still acceptable. We actually moved the guages and gained acouple of psi.
INSP-Sprinkler Rough-in6/30/20157/1/20157/1/2015APASS
DetailsTroy Cobbley
The remaining underground supply piping for the test header is ok for cover. Ball drip has been installed in vault.
INSP-Sprinkler Rough-in/Hydro6/24/20156/24/20156/24/2015PPASS
DetailsTroy Cobbley
Todays inspection was for the hanger area. Rough-in passed. Mike is going to provide verifircation that the two tech screws used for the 2" branchline hanger is approved. I need to verify that hanger clips are not required (data sheet provided with submittal)
INSP-Sprinkler Rough-in/Hydro6/15/20156/15/20156/15/2015PPASS
DetailsJim Page
Hydrostatic test complete on the three wet systems
INSP-Sprinkler Rough-in6/5/20156/5/20156/5/2015PPASS
DetailsKatie Marron
Rough-in of grid ceiling areas OK to cover. One sprinkler head overspaced in front office (south west of main door). Needs to be adjusted left to the adjacent 2x2 grid per drawing..
INSP-Sprinkler Rough-in5/7/20155/8/20155/8/2015APART
DetailsKatie Marron
Rough-in inspection for office area wet system. Ok to cover hard lid and grid ceiling areas. Notice items: aux. drain missing, flex drops for grid ceiling to be finalized and possible missed coverage/HVAC obstruction in mechanical bay.
Permit Ready to Issue  5/4/2015 DONE
all requirments met
Issue and Print Permit  5/4/2015 DONE
Inspection Record Card- Fire5/4/2015 5/4/2015 DONE
DetailsCarlos Velazquez
Sprinkler Plan Check5/1/2015 5/1/2015 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  5/1/2015 DONE
DetailsTim Frost
Miscellaneous action  4/28/2015 DONE
Spoke with Jeff Packham on Friday 4/24/2015. I told him it did not look like the heater system in his design met code. The code requirments would seem to indicate a circulating type heater system is required. The project is hold waiting for him to respond.
Sprinkler Plan Check3/6/2015 3/6/2015 FAIL
DetailsTim Frost
Miscellaneous action  3/6/2015 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Early Start  2/11/2015 PASS
See attached document
Sprinkler Plan Check12/8/2014 12/8/2014 FAIL
DetailsTim Frost
1st review completed  12/8/2014 FAIL
DetailsTim Frost
Miscellaneous action  12/8/2014 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Meeting  12/2/2014 DONE
Question and Answers from meeting via email.


Jeff,

Per NFPA 22 the tanks is required to be heated.

16.1.1 Tanks that are subject to freezing shall be heated.

The verbiage below or something similar is in many NFPA, if not all

1.4 Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength, fire resistance, effectiveness, durability,
and safety over those prescribed by this standard.

Jeff, you need find me some test results that show equivalency. The test results would need to be sealed and dated by a FPE, stating heating of the tank is not required. I can than review the information, and get fire code official approval, if it checks out satisfactorily.


Discharging back into the tank is fine. However, the nozzles discharging back into the tank are required to be listed and rated for 175%.

NFPA 20: 4.20.2.1* Metering devices or fixed nozzles for pump testing shall be listed.

NFPA 20: 4.20.2.2 Metering devices or fixed nozzles shall be capable of water flow of not less than 175 percent of rated pump capacity.

¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬
4.7.7* Maximum Pressure for Centrifugal Pumps.
4.7.7.1 The net pump shutoff (churn) pressure plus the maximum
static suction pressure, adjusted for elevation, shall not exceed
the pressure for which the system components are rated.
4.7.7.2* Pressure relief valves and pressure regulating devices
in the fire pump installation shall not be used as a means to
meet the requirements of 4.7.7.1.

4.18.1.1* Pressure relief valves shall be used only where specifically
permitted by this standard.
4.18.1.2 Where a diesel engine fire pump is installed and where
a total of 121 percent of the net rated shutoff (churn) pressure
plus the maximum static suction pressure, adjusted for elevation,
exceeds the pressure for which the system components are rated,
a pressure relief valve shall be installed.
4.18.1.3 Where an electric variable speed pressure limiting
controller or a diesel pressure limiting driver is installed, and
the maximum total discharge head adjusted for elevation with
the pump operating at shutoff and rated speed exceeds the
pressure rating of the system components, a pressure relief
valve shall be installed.

If you comply with the above, it seems NFPA 20 does not require a main relief valve.

You said 209#. The pipe and fittings will probably be ok. But what about the pressure switch, sprinklers, etc?

You will still of course still need a Circulation Relief Valve to keep the pump from overheating.

4.18.8* Discharge to Suction Reservoir. Where the supply of
water to the pump is taken from a suction reservoir of limited
capacity, the drain pipe shall discharge into the reservoir at a
point as far from the pump suction as is necessary to prevent the
pump from drafting air introduced by the drain pipe discharge.

You were concerned about the wasted water. It appears, you could simply discharge back to the tank.

I am still looking in the combustion air issue

Cordially,

Tim Frost, S.E.T.
Fire Sprinkler Plans Examiner
Fire Code Plans Examiner
Fire Inspector

City of Boise
tfrost@cityofboise.org
###-####


6.9 Air Supply.
6.9.1 Air from outside the hazard area shall be used for foam
generation unless data is provided to show that air from inside
the hazard can be successfully employed.
6.9.2 The data shall be specific for the products of combustion
to be encountered and shall provide factors for increasing
foam discharge rates over those given in 6.12.8 if fire tests
indicate that need.
6.9.3 Vents from the fire area shall be located to prevent recirculation
of combustion products or other materials deleterious
to the formation of foam into foam generator air inlets.

The above would seem to pertain to your situation.

Intake Approval  12/1/2014 PASS
Plan assigned to (Tim)12/1/2014 12/1/2014 DONE
DetailsTim Frost
Application received  11/13/2014 DONE
Application submitted via PDS Online on Nov 13 2014 1:31PM