Case Summary | | | 2/3/2015 | | |
|
|
|
|
INSP-Final Inspection | 11/24/2014 | 11/25/2014 | 11/25/2014 | A | PASS |
Forrest France
|
|
|
Previous correction items verified for completion. Necessary modifications and as-built plans finished. Functional testing and inspection passed, permit finaled.
|
INSP-Final Inspection | 11/23/2014 | 11/24/2014 | 11/24/2014 | A | FAIL |
Troy Cobbley
|
|
|
Strobes in Pizza and Customer Services areas have not been set for the correct candella which makes them currectly overspaced. Work shown near/in the Bakery has not been performed and if installed as per the plans will still be defiecient as discussed. Contractor shall contact plan review to verify whether as-builts will be adequate or if plan modifications will be required.
|
Permit Ready to Issue | | | 11/20/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Issue and Print Permit | | | 11/20/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 11/20/2014 | | 11/20/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Application received | | | 11/19/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Nov 19 2014 12:07PM
|
Plan assigned to (Lee) | 11/19/2014 | | 11/19/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 11/19/2014 | | PASS |
|
|
|
|
Alarm Plan Check | 11/19/2014 | | 11/19/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/19/2014 | | DONE |
|
|
|
Plans approved with review comments. Projectdox updated.
|