INSP-Final Inspection | 1/9/2015 | 1/9/2015 | 1/9/2015 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 12/28/2014 | 12/29/2014 | 12/29/2014 | A | FAIL |
Troy Cobbley
|
|
|
See alarm testing inspection for today for list of correction items needed.
|
INSP-Alarm Testing | 12/28/2014 | 12/29/2014 | 12/29/2014 | A | DONE |
Troy Cobbley
|
|
|
Tested function of the horn/strobes. Need as-builts showing the adjustment of the candella's and the addition of the duct smoke detector. And then testing of the duct smoke detector. Need weather proof backbox for the strobe over the pool. "Water Bug" may not be listed for use with acid.
|
Telephone call | | | 12/16/2014 | | DONE |
|
|
|
Brian, of Tribal Fire, call to say that there will be a duct detector added to the scope of work. I informed him that a plan modification submittal will be required. He also indicated that the general contractor has informe dhim that there are existing AHU's in the gym area that will require duct detectors. These gym ducts are not actually part of the current construction project. I told Brian that he can do these through a plan mod or under a new permit.
|
Plan assigned to (Lee) | 12/11/2014 | | 12/11/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 12/11/2014 | | PASS |
|
|
|
|
Alarm Plan Check | 12/11/2014 | | 12/11/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 12/11/2014 | | DONE |
|
|
|
Plans approved with review comments. Projectdox updated.
|
Permit Ready to Issue | | | 12/11/2014 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/11/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/11/2014 | | 12/11/2014 | | DONE |
Christina Prado
|
|
|
|
Application received | | | 12/8/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Dec 8 2014 8:20PM
|