Permit Information
Permit NumberFIR14-00898
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 1570 S LUSK PL
Project NameLusk Place Apartments
Customer Number 
ePlanReviewNo
Description
Provide a manual fire alarm system with sprinkler monitoring and low frequency notification in all sleeping areas. A voice system will be installed that is listed for the low frequency requirements. This permit is associated with building permit BLD14-00681.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  12/9/2015 DONE
INSP-Final Inspection8/6/20158/6/20158/6/2015PPASS
DetailsThomas Walsh
Final fire alarm system inspection. All system functions and operations tested OK. Could not put into service off-site due to many fire sprinklers still in trouble (valves closed) due to work that needed to be completed. All sprinkler systems are now in service and the FACP is cleared.
System will remain in service from this point on. As Builts were recently submitted to the city for review with some minor changes in SFDs, etc.
INSP-Final Inspection8/4/20158/4/20158/4/2015PPART
DetailsThomas Walsh
Completion of fire alarm system testing, including test os all HVAC shutdown SDS that were not operating last visit. Tested DP valves in PG, however one system (north side) did not operate correctly. Tested all notification devices in garage that were missing at last inspection.
Fire alarm system testing completed, except for fire sprinklers that need to be completed and retested.
INSP-Final Inspection8/3/20158/3/20158/4/2015PCANC
DetailsThomas Walsh
Canceled fire alarm testing for today - rescheduled for tomorrow (8/4).
INSP-Final Inspection7/30/20157/31/20157/31/2015APART
DetailsThomas Walsh
Continuation of fire alarm system testing, including a trip test of the 5 dry-pipe fire sprinkler systems (see FIR14-00815) for results of these tests.
Tested Elevator recall and shunt trip functions, completed testing of SDs for FSDs (all floors) HVAC shutdown SDs, and various SDs for panel rooms door closurers, etc. All tested OK.
The DDs used for HVAC shutdown should be changed to latching devices so that the system needs to be reset before the unit restarts.
Some device locations (descriptions) need to be changed to better decribe location or their purpose to aid respenders on locating the device in alarm. These will be rested next visit.
INSP-Final Inspection7/29/20157/30/20157/30/2015PPART
DetailsThomas Walsh
Initial fire alarm system testing, including all fire sprinkler interface for wet-pipe systems, SDs SFD, etc. Dry pipe systems not tested yet, including trip test of dry-pipe valves.
Issue and Print Permit  7/1/2015 DONE
Telephone call  3/6/2015 DONE
Rob Ahten call to indicate the 4 bedroom units have a soffit area that will prevent speaker mouniting at 90 inches. I indicated that through equivilent facilitation, he would be able to install them in these particular locations at at the closest available height. He indicated that they will only be a couple of inches from where planned.
Plan assigned to (Lee)12/10/2014 12/12/2014 DONE
DetailsLee G Meredith
1st review completed  12/12/2014 PASS
Alarm Plan Check12/12/2014 12/12/2014 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/12/2014 DONE
Plans approved with review comments. Taken to front desk for processing.
Permit Ready to Issue  12/12/2014 DONE
Telephone call  12/12/2014 DONE
DetailsCandy A. Nichols
called to talk to Daric but he was out. Told gentlemen that answered that the permit is ready and how much is owed. He will tell Deric
Inspection Record Card- Fire12/12/2014 12/12/2014 DONE
DetailsCandy A. Nichols
Application received  12/10/2014