INSP-Final Inspection | 5/6/2015 | 5/8/2015 | 5/8/2015 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 4/21/2015 | 4/23/2015 | 4/22/2015 | A | FAIL |
Troy Cobbley
|
|
|
Inspection actually performed on 4/21/2015 but not scheduled. Missing document box and it appears an additional monitor module is needed to monitor the new NAC panel. Also only one surge protector was installed at the FACP instead of the two as shown on the plans. As-builts needed showing these changes prior to a final sign off.
|
Telephone call | | | 4/14/2015 | | DONE |
|
|
|
Jeremy - We can have two inspectors available for the final inspection on this fire alarm project Tuesday April 21st at 1pm. We can commit up to two hours to perform this final inspection. I encourage your team to pre-test the system ahead of time to resolve any initiating device reporting issues or notification appliance synchronization/audibility issues prior to the City field inspectors arrival. This will expedite the field inspection process. The following items below will be points of emphasis during the final inspection:
• Smoke detectors will need to be smoked and report accurately to the FACP;
• Pull stations will be tested and checked for accurate reporting at the panel;
• Notifications appliances will be checked for location, functionality and synchronization in required areas;
• Verification of fire alarm system map with device addresses, function, and location to be at the panel within an approved cabinet;
• Verification of alarm reporting to the Central Service station monitoring facility will also be checked…
Scott Arellano
PDS/Fire Division
Plan Review and Field Inspection Supervisor
###-####
sarellano@cityofboise.org
|
INSP-Final Inspection | 4/1/2015 | 4/3/2015 | 4/3/2015 | P | DEFR |
Forrest France
|
|
|
Overbooked - need advance notice to confirm time and staffing available to complete inspection as requested.
|
INSP-Final Inspection | 3/23/2015 | 3/30/2015 | 3/30/2015 | P | DEFR |
Forrest France
|
|
|
|
Telephone call | | | 3/5/2015 | | DONE |
|
|
|
Ray of Alarmco call to see if it was acceptable to have double pole breakers powering multiple NAC panels at seperate buildings. I informed him that it was not allowed since a breaker tripping for one panel would affect another. Also, is a knox box required to gain access to the panel. I informed him that it was.
|
Permit Ready to Issue | | | 1/14/2015 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/14/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/14/2015 | | 1/14/2015 | | DONE |
Brittany Hill
|
|
|
|
Alarm Plan Check | 1/12/2015 | | 1/12/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/12/2015 | | DONE |
|
|
|
Resubmittal approved with review comments. Projectdox updated.
|
Plan resubmittals received | | | 1/9/2015 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 1/2/2015 | | 1/2/2015 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 1/2/2015 | | FAIL |
|
|
|
See 1st review comments.
|
Miscellaneous action | | | 1/2/2015 | | DONE |
|
|
|
Emailed applicant failed review comments.
|
Application received | | | 12/19/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Dec 19 2014 10:54AM
|