Permit Information
Permit NumberFIR15-00018
StatusFinaled
Name PEAK ALARM
Site Address 222 S AUTO DR
Project NameBoise Collision Repair Center
Customer Number 
ePlanReviewNo
Description
Addition of 5 new duct smoke detectors to an existing fire alarm system. Associated with building permit BLD14-00948.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  6/6/2016 DONE
Case Summary  2/5/2015  
INSP-Final Inspection1/29/20151/30/20151/30/2015APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/28/20151/29/20151/29/2015AFAIL
DetailsTroy Cobbley
Outside alarm bell did not ring upon activation of the dry pipe system.
Permit Ready to Issue  1/27/2015 DONE
Issue and Print Permit  1/27/2015 DONE
Issue and Print Permit  1/27/2015 DONE
Inspection Record Card- Fire1/27/2015 1/27/2015 DONE
DetailsBrittany Hill
Telephone call  1/26/2015 DONE
Received a call from the mechanical engineer of the project. He wanted to confirm that duct detectors are not being required. I did confirm that. He indicated that he will issue a notice to the architect and general contractor syaing that the ones installed on the supply dictwork can be removed.
Miscellaneous action  1/23/2015 DONE
Email sent to applicant to notify them that 2 copies of the resubmittal are required - not one and the they will need to provide an additional on prior to review.
Miscellaneous action  1/23/2015 DONE
Applicant is delivering a second copy of the plan mod application.
Alarm Plan Check1/23/2015 1/23/2015 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  1/23/2015 DONE
Quick permit plan mod submittal approved with no review comments. Taken to front desk for processing.
Telephone call  1/23/2015  
called Mary-left voicemail that permit is ready, remaining fees, and that we need a 2nd copy of application
Plan resubmittals received  1/23/2015 DONE
Two copies of Application and Documents.
Plan resubmittals received  1/22/2015 DONE
received one copy of application resubmittal
Telephone call  1/21/2015 DONE
Jason of Peak Alarm called to confirm that duct detectors were not required. I told him that they are not. He said that a new sprinkler riser was being added that is to be monitored. I told him to resubmit this under the same permit number as a plan modification.
Plan assigned to (Lee)1/12/2015 1/16/2015 DONE
DetailsLee G Meredith
1st review completed  1/16/2015 PASS
Alarm Plan Check1/16/2015 1/16/2015 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  1/16/2015 DONE
Plans approved with review comments, drawing notation and requirements. Taken to front desk for processing.
Permit Ready to Issue  1/16/2015 DONE
Telephone call  1/16/2015 DONE
DetailsCandy A. Nichols
called Jason Petty to let know permit is ready and how much is owed
Miscellaneous action  1/13/2015 DONE
I emailed Mary Froemke to let her know the the duct detectors shown on the drawing are not required and can be removed. This is based on IMC section 606.2 exception. I also informed her that if the mechanical engineer insists on having duct detection, the sensors will need to be installed on the return ducts instead of the supply ducts based on IMC section 606 . Mary responded to state that the detectors would still be installed on the supply side. She asked if they needed to be monitored. I responded stating that if the detectors were installed, it was to be on the retun side Per IMC or not at all and that if installed, they were required to be monitored Per NFPA 72..
Application received  1/12/2015