Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR15-00058
StatusFinaled
Name PROTEX
Site Address 10787 W USTICK RD
Project NameNorthpoint Recovery
Customer Number 
ePlanReviewYes
Description
Major remodel of an existing Primary Health facility into a detox center. Our scope is to provide a code compliant fire alarm system for the new occupancy classification and use. Associated with building permit BLD14-03504.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/6/20155/6/20155/6/2015PPASS
DetailsTroy Cobbley
permit finaled
Plan resubmittals received  5/6/2015 DONE
Plan mod received for added devices and as built drawings.
Alarm Plan Check5/6/2015 5/6/2015 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  5/6/2015 DONE
Plan mod approved. No additional review comments.
CHANGE STATUS TO (ISS)  5/6/2015 DONE
INSP-Final Inspection5/1/20155/4/20155/4/2015PFAIL
DetailsTroy Cobbley
Tested the two new smoke detectors. Can final when the plan modifications have been field verified.
INSP-Final Inspection4/30/20155/1/20155/1/2015AFAIL
DetailsTroy Cobbley
Two additional smoke detectors required in mens and womens lounge areas at vaulted ceilings. Plan modification required.
Plan resubmittals received  4/29/2015 DONE
Plan modification for added dry sprinkler system received.
Alarm Plan Check4/29/2015 4/29/2015 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  4/29/2015 DONE
Resubmittal approved with no review comments. Projectdox updated.
Permit Ready to Issue  4/29/2015 DONE
CHANGE STATUS TO (ISS)  4/29/2015 DONE
Telephone call  4/28/2015 DONE
Rob Ahten called to have the projectdox opened to upload a plan modification.
Permit Ready to Issue  1/28/2015 DONE
Issue and Print Permit  1/28/2015 DONE
Inspection Record Card- Fire1/28/2015 1/28/2015 DONE
DetailsKristal Soland
Miscellaneous action  1/28/2015 DONE
Plan redline markup had an error. Room 106 is noted as requiring a low frequency horn (if installed). The correct room number is 126.
Plan assigned to (Lee)1/27/2015 1/27/2015 DONE
DetailsLee G Meredith
Miscellaneous action  1/27/2015 DONE
Emailed Jonathan to let him know that the horn / strobes in 2 of the sleeping rooms (106 & 133) will need to be low frequency horns to meet 2013 NFPA 72 18.4.5.3 requirements for sleeping areas, if provided. No plan mod required.
1st review completed  1/27/2015 PASS
Alarm Plan Check1/27/2015 1/27/2015 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  1/27/2015 DONE
Plans approved with review comments and notation. Projectdox updated.
Application received  1/26/2015 DONE
Application submitted via PDS Online on Jan 26 2015 12:47PM