INSP-Final Inspection | 5/6/2015 | 5/6/2015 | 5/6/2015 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
Plan resubmittals received | | | 5/6/2015 | | DONE |
|
|
|
Plan mod received for added devices and as built drawings.
|
Alarm Plan Check | 5/6/2015 | | 5/6/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/6/2015 | | DONE |
|
|
|
Plan mod approved. No additional review comments.
|
CHANGE STATUS TO (ISS) | | | 5/6/2015 | | DONE |
|
|
|
|
INSP-Final Inspection | 5/1/2015 | 5/4/2015 | 5/4/2015 | P | FAIL |
Troy Cobbley
|
|
|
Tested the two new smoke detectors. Can final when the plan modifications have been field verified.
|
INSP-Final Inspection | 4/30/2015 | 5/1/2015 | 5/1/2015 | A | FAIL |
Troy Cobbley
|
|
|
Two additional smoke detectors required in mens and womens lounge areas at vaulted ceilings. Plan modification required.
|
Plan resubmittals received | | | 4/29/2015 | | DONE |
|
|
|
Plan modification for added dry sprinkler system received.
|
Alarm Plan Check | 4/29/2015 | | 4/29/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/29/2015 | | DONE |
|
|
|
Resubmittal approved with no review comments. Projectdox updated.
|
Permit Ready to Issue | | | 4/29/2015 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 4/29/2015 | | DONE |
|
|
|
|
Telephone call | | | 4/28/2015 | | DONE |
|
|
|
Rob Ahten called to have the projectdox opened to upload a plan modification.
|
Permit Ready to Issue | | | 1/28/2015 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/28/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/28/2015 | | 1/28/2015 | | DONE |
Kristal Soland
|
|
|
|
Miscellaneous action | | | 1/28/2015 | | DONE |
|
|
|
Plan redline markup had an error. Room 106 is noted as requiring a low frequency horn (if installed). The correct room number is 126.
|
Plan assigned to (Lee) | 1/27/2015 | | 1/27/2015 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 1/27/2015 | | DONE |
|
|
|
Emailed Jonathan to let him know that the horn / strobes in 2 of the sleeping rooms (106 & 133) will need to be low frequency horns to meet 2013 NFPA 72 18.4.5.3 requirements for sleeping areas, if provided. No plan mod required.
|
1st review completed | | | 1/27/2015 | | PASS |
|
|
|
|
Alarm Plan Check | 1/27/2015 | | 1/27/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/27/2015 | | DONE |
|
|
|
Plans approved with review comments and notation. Projectdox updated.
|
Application received | | | 1/26/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Jan 26 2015 12:47PM
|