Permit NumberFIR15-00082
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1150 N CURTIS RD
Project NameBOR GSA TI
Customer Number 
ePlanReviewYes
Description
[Bureau of Reclamation]
The fire sprinkler scope of work consists of modifying the existing system throughout the building per NFPA 13 for light hazard. The existing system will be upgraded with a new 4" backflow, riser, floor controls, 4" feed main, 4" primary main, 3” secondary main and 1¼” branch line. Existing 1 1/4" lines will stay in place with new arm overs and quick response heads.

Tenant Improvement to the interior of all three floors of this existing 79,369 building per plans.
Exterior site improvements will be made to bring parking and access up to current codes, addition of security fencing and addition of covered car and bike parking. Demo permit under BLD14-03598. All building sprinkler and alarm systems must be maintained. This building is fully Fire Sprinklered for area increase and has an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **SRZ**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/22/20159/23/20159/23/2015APASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in/Hydro9/8/20159/8/20159/8/2015PPASS
DetailsTroy Cobbley
Overhead hydro test and rough to cover of the third floor passed. Piping can be covered.
INSP-Sprinkler Rough-in8/19/20158/20/20158/20/2015APART
DetailsJim Page
Notated area's approved for with red ink on the city approved drawings. Area's inspected, male & female entry/restrooms on 3rd floor.
INSP-Sprinkler Rough-in/Hydro5/5/20155/6/20155/6/2015APASS
DetailsKatie Marron
1st floor hydrostatic test passed.
INSP-Sprinkler Rough-in/Hydro5/4/20155/5/20155/5/2015APART
DetailsTroy Cobbley
First floor hydro test failed. Rough-in passed. Contractor to provide sheet rock on exposed wood at accordian door. And per contractor there will be no storage of paper in the Copy Center there fore light hazard spacing is ok.
INSP-Sprinkler Rough-in/Hydro4/20/20154/20/20154/20/2015PPASS
DetailsTroy Cobbley
Second floor hydro test passed
INSP-Sprinkler Rough-in/Hydro4/16/20154/17/20154/17/2015ACANC
DetailsTroy Cobbley
Cancel per Matt due to leaks
INSP-Sprinkler Rough-in4/16/20154/16/20154/16/2015PPASS
DetailsTroy Cobbley
Second floor sprinkler piping is ok to cover.
INSP-Sprinkler Rough-in3/18/20153/18/20153/18/2015PPASS
DetailsTroy Cobbley
See the city approved plans for Womens Restroom, first floor, where piping is ok to cover as marked "ok" on the city approved plans.
INSP-Sprinkler Rough-in3/9/20153/9/20153/10/2015PPASS
DetailsTroy Cobbley
See city approved plans for locations marked ok where piping can be covered. Areas include mens and womens showers
Permit Ready to Issue  2/12/2015 DONE
Issue and Print Permit  2/12/2015 DONE
Inspection Record Card- Fire2/12/2015 2/12/2015 DONE
DetailsChristina Prado
Sprinkler Plan Check2/11/2015 2/11/2015 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  2/11/2015 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  2/11/2015 DONE
DetailsTim Frost
Intake Approval  2/10/2015 PASS
Plan assigned to (Tim)2/10/2015 2/10/2015 DONE
DetailsTim Frost
Application received  2/4/2015 DONE
Application submitted via PDS Online on Feb 4 2015 9:07AM