Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR15-00095
StatusFinaled
Name TYCO INTEGRATED SECURITY
Site Address 1200 N CLOVERDALE RD
Project NameCloverdale Funeral Home
Customer Number 
ePlanReviewYes
Description
Disconnect and remove three smoke detectors in the crematorium due to false alarm problem cuased by excessive dust. Area is still covered by two heat detectors and sprinklers. Two additional heat detectors are being added to meet derating requirements due to ceiling heights. This project is not associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/18/20152/23/20152/23/2015APASS
DetailsForrest France
Scope of fire alarm work completed and passed functional testing. Permit finaled.
Permit Ready to Issue  2/12/2015 DONE
Issue and Print Permit  2/12/2015 DONE
Inspection Record Card- Fire2/12/2015 2/12/2015 DONE
DetailsChristina Prado
Plan resubmittals received  2/11/2015 DONE
Alarm Plan Check2/11/2015 2/11/2015 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/11/2015 DONE
Quick permit approved with no review comments. Projectdox updated.
Application received  2/6/2015 DONE
Application submitted via PDS Online on Feb 6 2015 9:25AM
Plan assigned to (Lee)2/6/2015 2/6/2015 DONE
DetailsLee G Meredith
1st review completed  2/6/2015 FAIL
Review failed due to lack of information. I emailed Dale Hurd to let him know that ceiling heights and slope calculations will need to be provided to determine heat detector spacing requirements. Also, a scaled drawing will be required with this information.