INSP-Final Inspection | 5/27/2015 | 5/28/2015 | 5/29/2015 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Issue and Print Permit | | | 5/26/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/26/2015 | | 5/26/2015 | | DONE |
Brittany Hill
|
|
|
|
Plan resubmittals received | | | 5/18/2015 | | DONE |
|
|
|
Plan mod received to reflect removed smoke detectors noted in the 5/12/15 inspection.
|
Alarm Plan Check | 5/18/2015 | | 5/18/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/18/2015 | | DONE |
|
|
|
Plan Modification approved with no new review comments. Taken to front desk for processing.
|
Permit Ready to Issue | | | 5/18/2015 | | DONE |
|
|
|
Fees Due. DO NOT RE-ISSUE Plan Mod
|
Telephone call | | | 5/18/2015 | | DONE |
|
|
|
Informed Eric that plans turned in for modification is ready and that there is a fee of 150.
|
INSP-Alarm Testing | 5/5/2015 | 5/12/2015 | 5/12/2015 | A | FAIL |
Troy Cobbley
|
|
|
Horn/strobe has been added to Laundry Room, smoke detectors have not been added to the Garden Room, knox box installed, map installed, set off notification and found that sync'ing is an issue with the sound and possibly with the strobes. I stopped the inspection of the horn/strobes as not to continue dicomfort of the tenants.
|
INSP-Alarm Testing | 4/13/2015 | 4/16/2015 | 4/16/2015 | A | CANC |
Troy Cobbley
|
|
|
Called contacts phone at 9:00am and left message for working out an inspection time. Stopped at project at 9:45 to see is contact was on site but found no one. I let Scott know. I later received phone call stating that the number is a wrong number. Eric Phone #: ###-####
|
INSP-Alarm Testing | 4/13/2015 | 4/15/2015 | 4/16/2015 | P | DONE |
Troy Cobbley
|
|
|
Todays inspection consisted of verifying that the panel model, NAC model, phone lines, batteries, wire guage at the FACP, revised horn/strobe layout and initial smoke detector layout was correct. Noted corrections are missing smoke detectors in the Garden Room, need strobe coverage in Laundry Room in Memory Care and possible strobe coverage in the east corridor area just outside of Memory Care. Also no sprinkler devices were checked. Missing Knox box and map at the FACP. Need to verify all requirements in the review comments and the revised drawings have been met.
|
Telephone call | | | 4/14/2015 | | DONE |
|
|
|
Mr. Pettichord -
In regards to the Final Field Inspection request. We will have two inspectors available for the final inspection on this fire alarm project Wednesday April 15th at 1pm. We can commit up to two hours to perform this final inspection. I encourage your team to pre-test the system ahead of time to resolve any initiating device reporting issues or notification appliance synchronization/audibility issues prior to the City field inspectors arrival. This will expedite the field inspection process. The following items below will be points of emphasis during the final inspection:
• Smoke detectors will need to be smoked and report accurately to the FACP;
• Pull stations will be tested and checked for accurate reporting at the panel;
• Notifications appliances will be checked for location, functionality and synchronization in required areas;
• Verification of fire alarm system map with device addresses, function, and location to be at the panel within an approved cabinet;
• Verification of alarm reporting to the Central Service station monitoring facility will also be checked…
Please pass this information along to all pertinent personnel who may be participating in the inspection process.
Regards,
Scott Arellano
PDS/Fire Division
Plan Review and Field Inspection Supervisor
###-####
sarellano@cityofboise.org
|
Plan assigned to (Lee) | 3/30/2015 | | 4/13/2015 | | DONE |
Lee G Meredith
|
|
|
|
Alarm Plan Check | 4/13/2015 | | 4/13/2015 | | PASS |
Lee G Meredith
|
|
|
Revised plans re-issued reflecting fire inspectors comments on initial field inspection.
|
PLANS TAKEN FRONT DESK ALARM | | | 4/13/2015 | | DONE |
|
|
|
As built drawings approved without additional review comment. No fee due. Taken to front desk for processing.
|
Permit Ready to Issue | | | 4/13/2015 | | DONE |
Christina Prado
|
|
|
No fees due per LGM
|
Inspection Record Card- Fire | 4/13/2015 | | 4/13/2015 | | DONE |
Christina Prado
|
|
|
|
CHANGE STATUS TO (ISS) | | | 4/13/2015 | | DONE |
|
|
|
Plan Mod
|
CHANGE STATUS TO (REV) | | | 4/9/2015 | | DONE |
|
|
|
as per Scott A. change to rev
|
INSP-Final Inspection | 4/1/2015 | 4/2/2015 | 4/2/2015 | P | CANC |
Troy Cobbley
|
|
|
Overbooked. Will need to be rescheduled. I let Eric know.
|
Plan resubmittals received | | | 3/30/2015 | | DONE |
|
|
|
PLAN MOD. Two copies of sheets FA-1,FA-2, FA-3, FA-4 and FA-5
|
INSP-Alarm Testing | 3/23/2015 | 3/26/2015 | 3/26/2015 | P | FAIL |
Troy Cobbley
|
|
|
Plans need to be re-submitted showing the additional notification devices needed and relocated NAC panels and NAC panel triggers. Several strobes are overspaced. Alot of old devices have not been removed. Strobes need to be added in common restrooms and Linen Rooms/Laundery Rooms. There are ceiling obstructions that effect strobe placement and smoke detector placement.
|
Issue and Print Permit | | | 3/17/2015 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/11/2015 | | DONE |
Candy A. Nichols
|
|
|
|
Inspection Record Card- Fire | 3/11/2015 | | 3/11/2015 | | DONE |
Candy A. Nichols
|
|
|
|
Telephone call | | | 3/11/2015 | | DONE |
Candy A. Nichols
|
|
|
called Mark to let know permit is ready
|
Application received | | | 3/10/2015 | | |
|
|
|
|
Plan assigned to (Lee) | 3/10/2015 | | 3/10/2015 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 3/10/2015 | | PASS |
|
|
|
|
Alarm Plan Check | 3/10/2015 | | 3/10/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/10/2015 | | DONE |
|
|
|
Plans approved with review comments and drawing notation. Taken to front desk for processing.
|