Permit Information
Permit NumberFIR15-00153
StatusFinaled
Name PROTEX
Site Address 3100 S VISTA AVE Unit: 200
Project NameI.C.R.M.P. 2nd Floor Remodel
Customer Number 
ePlanReviewYes
Description
Modification of the building's existing fire alarm system to incorporate new non-profit governmental organizations as tenants on the 2nd floor. Plan modification submitted 6-16-15. Owner has decided to replace the existing fire alarm panel. Plan modification received 8-28-15 to change some wall strobes ceiling and changes to sprinkler and elevator monitoring. Associated with building permit BLD14-03099.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  12/9/2015 DONE
INSP-Final Inspection9/2/20159/3/20159/3/2015APASS
DetailsJim Page
Final fire alarm inspection passed/complete
CHANGE STATUS TO (ISS)  9/2/2015 DONE
plan mod fees paid
Plan resubmittals received  9/1/2015 DONE
Alarm Plan Check9/1/2015 9/1/2015 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/1/2015 DONE
Resubmittal of plan mod 2 approved with review comments.
Plan resubmittals received  8/28/2015 DONE
Plan modification recieved. Numerous wall strobes moved to ceiling. Changes on sprinkler monitoring and elevator status light.
CHANGE STATUS TO (REV)  8/28/2015 DONE
Alarm Plan Check8/28/2015 8/28/2015 FAIL
DetailsLee G Meredith
See Plan Mod 2 review comments.
INSP-Final Inspection8/26/20158/26/20158/26/2015PFAIL
DetailsTroy Cobbley
The only items test today was verifying the facp and nac panels, phone lines, elevator recall and fire sprinkler flow and tamper switches. I noted that the elevator power needs to be monitored but hat functions can remain as-is, all of the wall mount strobes are mounted too low, many of the strobes are overspaced, additional notification devices are required on the third floor in the areas that are to remain occupied. As-builts with these corrections and corrected floor plan layout will be required. I did not inspect any of the first floor or basement today.
Telephone call  8/26/2015 DONE
Rob Ahten call to say they found a sprinkler head in the elevator shaft and added a smoke and heat there that ware tied to recall and shunt. I told him that we would not require a resubmittal but would require as built drawings sent in for archiving. Called Troy to let him know.
Plan resubmittals received  6/17/2015 DONE
Alarm Plan Check6/17/2015 6/17/2015 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/17/2015 DONE
Resubmittal of plan mod approved with review comments. Projectdox updated.
CHANGE STATUS TO (ISS)  6/17/2015 DONE
Plan resubmittals received  6/16/2015 DONE
Plan modification to replace the existing fire alarm panel and related components.
CHANGE STATUS TO (REV)  6/16/2015 DONE
Changed to review status for plan modification.
1st review completed  6/16/2015 FAIL
See 6-16-15 review comments.
Telephone call  6/15/2015 DONE
Jonathan call to request the work flow be reopened. Owner has decided to add panel replacement to the scope of work.
Permit Ready to Issue  3/12/2015 DONE
Issue and Print Permit  3/12/2015 DONE
Inspection Record Card- Fire3/12/2015 3/12/2015 DONE
DetailsChristina Prado
Plan assigned to (Lee)3/11/2015 3/11/2015 DONE
DetailsLee G Meredith
1st review completed  3/11/2015 PASS
Alarm Plan Check3/11/2015 3/11/2015 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/11/2015 DONE
Plans approved with review comments. Projectdox updated.
Application received  3/10/2015 DONE
Application submitted via PDS Online on Mar 10 2015 10:39AM