INSP-Final Inspection | 1/19/2017 | 1/23/2017 | 1/23/2017 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection passed/complete.
|
INSP-Final Inspection | 11/21/2016 | 11/22/2016 | 11/22/2016 | A | PART |
Jim Page
|
|
|
Partial final inspection complete for annex builing, audio visual devices for level 1 through 4 of annex complete, commercial hood suppression system monitoring complete for level 4.
|
INSP-Alarm Testing | 11/21/2016 | 11/22/2016 | 11/21/2016 | P | CANC |
Jim Page
|
|
|
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Monday, November 21, 2016.
|
INSP-Alarm Testing | 11/17/2016 | 11/18/2016 | 11/18/2016 | A | DONE |
Jim Page
|
|
|
Alarm testing for hood suppression systems on level 4 complete.
|
INSP-Alarm Testing | 11/17/2016 | 11/17/2016 | 11/17/2016 | P | CANC |
Jim Page
|
|
|
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Thursday, November 17, 2016.
|
INSP-Alarm Testing | 11/15/2016 | 11/15/2016 | 11/15/2016 | P | DONE |
Jim Page
|
|
|
Alarm testing complete for smokes and in-ducts for annex, fire sprinkler flow and tamper switches tested and passed, level 4 flow switch needs to be replaced and retested.
|
INSP-Final Inspection | 11/14/2016 | 11/14/2016 | 11/14/2016 | A | PART |
Jim Page
|
|
|
Fire alarm testing complete for heat and smoke detectors on the simplot world headquarters basement level.
|
INSP-Final Inspection | 10/27/2016 | 10/27/2016 | 10/27/2016 | P | PART |
Jim Page
|
|
|
Partial final inspection complete for fire alarm system in Simplot World Headquarters. Final inspection still needs to happen for parking garage and annex.
|
INSP-Alarm Testing | 10/26/2016 | 10/26/2016 | 10/26/2016 | P | DONE |
Jim Page
|
|
|
Alarm testing complete for today. Items tested: Floor above floor below notification for all levels of the headquarters building levels parking through 9, automatic shutdown from in duct detection for air handler units 1,2 and 3, audio visual verification for headquarters stack 1 and 2 of level 1 and headquarters parking level, verified signals received from monitoring service, rooftop exhaust unit shutdown and heat trace monitoring for headquarters heat trace on fire sprinkler mains.
|
INSP-Alarm Testing | 10/25/2016 | 10/25/2016 | 10/25/2016 | P | DONE |
Jim Page
|
|
|
Automatic stairwell pressurization, horizontal door operation in general alarm testing complete.
|
INSP-Alarm Testing | 10/20/2016 | 10/20/2016 | 10/20/2016 | P | DONE |
Jim Page
|
|
|
Alarm testing complete for tamper switches and flow switches on wet pipe fire sprinkler systems located on levels 1 through 9 (signal verification still needs to be performed on level 1 simplot tower dry system). Items that still need inspected: audio/visual signals on parking level dry/standpipe systems as well as dry/standpipe systems being supplied from the JUMP fire pump, audio/visual devices on level 1 and parking level, elevator recall on all elevators, emergency fire door on level 1, in duct and smoke detectors on level 1 and parking level, stairwell pressurization on general alarm, fire alarm interface with kitchen hood monitoring and signal verification for commercial hood fire suppression activation, all fire alarm components associated with annex building and monitoring verification.
|
INSP-Alarm Testing | 10/13/2016 | 10/17/2016 | 10/17/2016 | P | CANC |
Jim Page
|
|
|
Inspection request rescheduled for 18OCT2016
|
INSP-Alarm Testing | 10/13/2016 | 10/17/2016 | 10/17/2016 | A | CANC |
Jim Page
|
|
|
Inspection request re-scheduled for 18OCT2016
|
INSP-Alarm Testing | 10/13/2016 | 10/14/2016 | 10/14/2016 | P | DONE |
Jim Page
|
|
|
Alarm testing complete for in-duct detectors with damper closing, electrical room smoke detectors and fire door release on levels 4, 3 and 2.
|
INSP-Alarm Testing | 10/13/2016 | 10/14/2016 | 10/14/2016 | A | DONE |
Jim Page
|
|
|
Alarm testing complete for in-duct detectors with damper closing, electrical room smoke detectors and fire door release on levels 7,6 and 5.
|
INSP-Alarm Testing | 10/13/2016 | 10/13/2016 | 10/13/2016 | P | CANC |
Jim Page
|
|
|
Alarm testing rescheduled for following day due to inspection load.
|
INSP-Alarm Testing | 10/12/2016 | 10/12/2016 | 10/12/2016 | P | DONE |
Jim Page
|
|
|
In duct detectors tested on levels 8 & 9, door release tested on levels 8 & 9. Devices tested correctly.
|
INSP-Alarm Testing | 10/7/2016 | 10/7/2016 | 10/7/2016 | P | DONE |
Jim Page
|
|
|
Alarm testing complete for today, testing will resume on 10OCT2016
|
INSP-Alarm Testing | 10/5/2016 | 10/5/2016 | 10/5/2016 | P | CANC |
Jim Page
|
|
|
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Wednesday, October 05, 2016.
|
INSP-Alarm Testing | 10/3/2016 | 10/4/2016 | 10/4/2016 | P | DONE |
Jim Page
|
|
|
Audio visual device testing for levels 9 through 2 on main building complete, all A/V's on noted levels operated correctly.
|
INSP-Alarm Testing | 10/3/2016 | 10/3/2016 | 10/3/2016 | P | CANC |
Jim Page
|
|
|
Call for access Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Monday, October 03, 2016.
|
INSP-Conference | 6/2/2016 | 6/3/2016 | 6/3/2016 | A | DONE |
Jim Page
|
|
|
Fire conference complete, discussed height modifications for exterior A/V devices (total of 9 at various exterior locations), due to exterior design A/V devices will be mounted at 10ft 6in off of finish floor.
|
INSP-Conference | 2/2/2016 | 2/2/2016 | 2/2/2016 | P | DONE |
Jim Page
|
|
|
Conference complete
|
Telephone call | | | 12/7/2015 | | DONE |
|
|
|
Charlie called to see if they could omit the installation of remote test stations for all duct smoke detectors. I informed him that they are not required by code and could be removed. He will show this on as built drawings.
|
Telephone call | | | 9/11/2015 | | DONE |
|
|
|
Dante call to see if a plan modification submittal will be required for heat trace monitoring that is being added by the sprinkler contractor. I told him that as built drawings will be adequate.
|
Permit Ready to Issue | | | 8/31/2015 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/31/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/31/2015 | | 8/31/2015 | | DONE |
Christina Prado
|
|
|
|
Alarm Plan Check | 8/28/2015 | | 8/28/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 8/28/2015 | | DONE |
|
|
|
3rd resubmittal approved with review comments and conditions.
|
Plan resubmittals received | | | 8/25/2015 | | DONE |
|
|
|
|
Miscellaneous action | | | 8/17/2015 | | DONE |
|
|
|
2nd review failed. New review comments sent to Dante.
|
Plan resubmittals received | | | 8/14/2015 | | DONE |
|
|
|
Resubmittals received. Dante called to say that drawings 31 - 35 will no longer be used. I told him that I would stamp them VOID.
|
Miscellaneous action | | | 4/2/2015 | | DONE |
|
|
|
Email sent to Dante and Charlie with 1st review comments and fire marshall and building official approved alternate provision letters.
|
1st review completed | | | 4/2/2015 | | FAIL |
|
|
|
See 1st review comments.
|
Plan assigned to (Lee) | 3/30/2015 | | 3/30/2015 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 3/30/2015 | | DONE |
|
|
|
I emailed Dante and Charlie to let them know a 2 way radio communications system will be required instead of the wired fire phones that they designed.
|
Application received | | | 3/27/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 27 2015 4:54PM
|