INSP-Final Inspection | 8/5/2015 | 8/6/2015 | 8/6/2015 | P | CANC |
Troy Cobbley
|
|
|
Phone #: 2088705073 >> Inspection requested via mobile web by John Siewert Inspection cancelled from web by: Chris Siewert
|
INSP-Final Inspection | 5/20/2015 | 5/21/2015 | 5/22/2015 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 5/18/2015 | 5/19/2015 | 5/19/2015 | P | FAIL |
Troy Cobbley
|
|
|
1. Monitoring service not set up correctly. 2. All devices will need to be retested. 3. Need to provide knox box. 4. Provide document cabinet.
|
INSP-Final Inspection | 5/13/2015 | 5/14/2015 | 5/14/2015 | A | FAIL |
Troy Cobbley
|
|
|
No testing performed. Duct smoke detectors are not wired up or tested, smoke detector at the FACP is mounted too far from the deck, the tamper switch fot the PIV is not installed. I have not looked at the approved drawings yet.
|
Permit Ready to Issue | | | 4/27/2015 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/27/2015 | | DONE |
|
|
|
|
(F) Reprint permit | | | 4/27/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/27/2015 | | 4/27/2015 | | DONE |
Carlos Velazquez
|
|
|
|
Application received | | | 4/24/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 24 2015 1:48PM
|
Plan assigned to (Lee) | 4/24/2015 | | 4/24/2015 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 4/24/2015 | | PASS |
|
|
|
|
Alarm Plan Check | 4/24/2015 | | 4/24/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/24/2015 | | DONE |
|
|
|
Plans approved with review comments. Projectdox updated.
|