Case Summary | | | 12/8/2015 | | DONE |
|
|
|
|
INSP-Final Inspection | 8/19/2015 | 8/19/2015 | 8/19/2015 | P | PASS |
Jim Page
|
|
|
Previously noted items corrected, final alarm inspection passed/complete
|
INSP-Final Inspection | 8/18/2015 | 8/18/2015 | 8/18/2015 | P | PART |
Jim Page
|
|
|
Previously noted items not corrected, still need label on door for FACP Room, no document cabinet at FACP and no floor plan with initiating devices posted at FACP
|
INSP-Final Inspection | 5/5/2015 | 5/6/2015 | 5/6/2015 | P | PART |
Katie Marron
|
|
|
Partial final pass. Functional alarm test complete with the exception of flow switches on risers 1 & 2. Prior to final the following items to be completed: provide updated plans, provide knox box, provide document box, "Fire Alarm Control Panel" signage on doors, floor plan with initiating devices posted at FACP, and repaint alarm bell and add call 911 when sounding verbage.
|
INSP-Sprinkler Rough-in/Hydro | 5/5/2015 | 5/6/2015 | 5/5/2015 | P | CANC |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2089414511 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Tuesday, May 05, 2015.
|
Permit Ready to Issue | | | 5/5/2015 | | DONE |
|
|
|
all requirments met
|
Issue and Print Permit | | | 5/5/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/5/2015 | | 5/5/2015 | | DONE |
Carlos Velazquez
|
|
|
|
Miscellaneous action | | | 5/4/2015 | | DONE |
|
|
|
Dante Frassa called to have the work flow restarted so he could modify the drawings with prior to review. To restart the work flow, prescreen was failed. Revised drawings were later uploaded.
|
Plan assigned to (Lee) | 5/4/2015 | | 5/4/2015 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 5/4/2015 | | PASS |
|
|
|
|
Alarm Plan Check | 5/4/2015 | | 5/4/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/4/2015 | | DONE |
|
|
|
Plans approved with review comments and requirements. Projectdox updated.
|
Application received | | | 4/30/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 30 2015 1:16PM
|