Permit Information
Permit NumberFIR15-00304
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 3724 S ECKERT DR
Project NameHarris Ranch Mixed Use
Customer Number 
ePlanReviewYes
Description
TVFP WILL INSTALL A COMPLETE AUTOMATIC WET PIPE SPRINKLER SYSTEM THROUGHOUT THE NEW BUILDING PER NFPA 13. THE FIRST FLOOR IS A SHELL SPACE PROTECTED OH II AND THE 2 UPPER FLOORS ARE APARTMENTS PROTECTED LH WITH RESIDENTIAL HEADS AND CPVC PER NFPA 13.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/2/20173/2/20173/2/2017PPASS
DetailsJim Page
Final fire sprinkler inspection pased/complete.
INSP-Sprinkler Rough-in9/6/20169/6/20169/6/2016PPASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping located on level 3 was completed on 09AUG2016, overhead fire sprinkler piping on level 3 including higher ceilings in apartments approved for cover.
INSP-Sprinkler Rough-in/Hydro8/18/20168/19/20168/19/2016APASS
DetailsJim Page
200 psi hydrostatic test for level 2 complete . Rough to cover inspection for overhead fire sprinkler piping on level 2 complete, overhead fire sprinkler piping located on level 2 approved for cover.
INSP-Sprinkler Rough-in/Hydro8/15/20168/15/20168/15/2016APASS
DetailsJim Page
Rough to cover inspection complete for level 1, overhead fire sprinkler piping on level 1 approved for cover. 200 psi hydrostatic test for overhead fire sprinkler piping located on level 1 complete.
INSP-Sprinkler Rough-in/Hydro8/11/20168/12/20168/11/2016ACANC
DetailsJim Page
Inspection request rescheduled by me for 15AUG2016 per conversation with point of contact, Rudy Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro8/8/20168/9/20168/9/2016APART
DetailsJim Page
200 psi hydrostatic test for overhead fire sprinkler piping located on level 3 complete.
Sprinkler Plan Check5/26/2015 5/26/2015 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  5/26/2015 DONE
DetailsTim Frost
Permit Ready to Issue  5/26/2015 DONE
Issue and Print Permit  5/26/2015 DONE
Inspection Record Card- Fire5/26/2015 5/26/2015 DONE
DetailsCandy A. Nichols
Sprinkler Plan Check5/18/2015 5/18/2015 FAIL
DetailsTim Frost
Miscellaneous action  5/18/2015 DONE
Lighting versus sprinkler head locations.

Hi Tim,

I've attached the best information we have at this time, the approved lighting plans. They show the design locations. I'm also attaching the light fixture schedule. Most of the ceiling fixtures are either a recessed can, or mount to a standard back box, I believe.

I'm not sure we can provide the precision you're looking for. Most of the time, the reason a light fixture (or mechanical device) is relocated in the field is due to framing conflicts. We cannot know the final location of the framing, since the structural engineer only specifies a minimum spacing for the joists that make up the bulk of the floor framing. The contractor can start the layout wherever they want as long as they meet the minimum spacing.

Nathan already has the lighting layouts and I believe has included them on his drawings.

Thanks

Doug Cooper, AIA, LEED AP
McKibben + Cooper Architects
Architecture + Urban Design
519 W. Hays St.
Boise, ID 83702
208 343 7851
www.mckibbencooper.com

On May 18, 2015, at 10:06 AM, Tim Frost wrote:


Doug,

I do the fire sprinkler plan review for the City of Boise. I am working on your project named “Harris Ranch Mixed Use”. Treasure Valley Fire Protection is performing the fire protection work. I have asked them in a review comment to coordinate the sprinkler locations with the lighting fixtures. I asked them to stay 3’ away from the light fixtures to prevent obstruction issues.

During the final inspection on some projects the field inspectors have found the light fixtures are too close to the sprinklers. The City has then been forced to delay occupancy until the problem items are resolved. I am attempting to avoid this situation on this project and all future projects.

When I asked Treasure Valley Fire Protection to coordinate their sprinkler locations, they said the exact locations of the light fixtures were unknown at this time. Would you be able to supply Treasure Valley Fire Protection with exact locations and sizes of the light fixtures? I believe this would be beneficial to all involved parties. The person at Treasure Valley Fire Protection to contact is Nathan Stenquist (nathans@tvfp.us). As always, if you should have any questions please feel free to contact me.

Cordially,

Tim Frost, S.E.T.

Tim Frost, S.E.T.
Fire Sprinkler Plans Examiner
Planning & Development Services

Phone: ###-####
E-Mail: tfrost@cityofboise.org

150 North Capitol Boulevard
Boise, ID. 83701



Sprinkler Plan Check5/12/2015 5/12/2015 FAIL
DetailsTim Frost
1st review completed  5/12/2015 FAIL
DetailsTim Frost
Miscellaneous action  5/12/2015 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Intake Approval  5/8/2015 PASS
Plan assigned to (Tim)5/8/2015 5/8/2015 DONE
DetailsTim Frost
Application received  5/4/2015 DONE
Application submitted via PDS Online on May 4 2015 8:37AM