Miscellaneous action | | | 11/4/2015 | | DONE |
|
|
|
Mary Froemke to email as built documents today or tomorrow.
|
INSP-Final Inspection | 9/25/2015 | 9/25/2015 | 9/25/2015 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Alarm Testing | 6/1/2015 | 6/2/2015 | 6/2/2015 | A | PART |
Troy Cobbley
|
|
|
A temporary is being given until the door mag in the warehouse has been addressed.
|
INSP-Alarm Testing | 5/29/2015 | 6/1/2015 | 6/1/2015 | A | DONE |
Troy Cobbley
|
|
|
The water flow pressure switch now functions. Still need the low air switch re-programmed the door mags and lightning protection in the warehouse addressed.
|
INSP-Alarm Testing | 5/26/2015 | 5/27/2015 | 5/27/2015 | P | FAIL |
Troy Cobbley
|
|
|
The low air signal needs to be a "supervisory" signal, not an alarm signal. The "waterflow" pressure switch on the pre-action system did not activate upon the trip of the system.
|
Permit Ready to Issue | | | 5/22/2015 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/22/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/22/2015 | | 5/22/2015 | | DONE |
Christina Prado
|
|
|
|
1st review completed | | | 5/20/2015 | | PASS |
|
|
|
|
Alarm Plan Check | 5/20/2015 | | 5/20/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/20/2015 | | DONE |
|
|
|
Plans approved with review comments and requirements. Projectdox updated.
|
Plan resubmittals received | | | 5/19/2015 | | DONE |
|
|
|
|
Telephone call | | | 5/18/2015 | | DONE |
|
|
|
Ken call to say the designer had missed a warehouse building and HVAC systems that will both require additional fire alarm changes. He wanted to know if this could be submitted with the existing permits or if they should be new permits. I informed him they could be on the existing permit when he resubmits or they could be on new permits if partial occupancies are required.
|
Plan assigned to (Lee) | 5/11/2015 | | 5/11/2015 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 5/11/2015 | | DONE |
|
|
|
Ken Webster emailed a request to reopen the work flow so he can make some changes.
|
Application received | | | 5/9/2015 | | DONE |
|
|
|
Application submitted via PDS Online on May 9 2015 3:37PM
|