Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR15-00361
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1406 N FRY LN
Project Name#1406 Aberdeen 4-Plex Phase 4
Customer Number 
ePlanReviewYes
Description
[Aberdeen 4-Plex Phase 4 #1406 - Building #7]
CPVC piping is being used with extended coverage residential sprinklers to protect a two level, four unit apartment building using NFPA 13R

The underground is under permit FIR15-00353

L8B1 - 1406 Fry (Bldg 7): To construct a new 3,909 sq. ft., two story, Four unit, apartment building. Each unit has two bedrooms and two bathrooms. 1st story unit 101 is 959 square feet, unit 102 is 1,007 square feet, and both are required to be Type 'B' units. 2nd story unit 201 is 959 square feet and unit 202 has 984 square feet. All units share a common path of egress into and through a 1/2-hour rated exit corridor with 20 minute fire-resistive, listed, labeled, self-closing door assemblies from the dwelling units into the corridor. All construction per the approved plans, attached plan review report, and all other reviewing agencies approvals. One hour fire-partitions and one hour horizontal assemblies are required between dwelling units. This building is required to be fire sprinklered. The fire sprinkler system shall be per NFPA 13R as regulated by the fire department. DRH13-00276 & CUP13-00017 Per Planning and Zoning. **SRZ*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/24/20158/25/20158/25/2015APASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro7/13/20157/14/20157/14/2015APASS
DetailsTroy Cobbley
Overhead hydro test passed
Intake Approval  5/27/2015 PASS
Plan assigned to (Tim)5/27/2015 5/27/2015 DONE
DetailsTim Frost
Sprinkler Plan Check5/27/2015 5/27/2015 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  5/27/2015 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  5/27/2015 DONE
DetailsTim Frost
Permit Ready to Issue  5/27/2015 DONE
Issue and Print Permit  5/27/2015 DONE
Inspection Record Card- Fire5/27/2015 5/27/2015 DONE
DetailsKristal Soland
Application received  5/23/2015 DONE
Application submitted via PDS Online on May 23 2015 10:41AM