Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR15-00397
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 533 E PARKCENTER BLVD
Project NameThe District: In-Town # B-1
Customer NumberUDG ONLY
ePlanReviewYes
Description
[The District - Intown Building B - #1 - Udg Only] - Quick Permit
Shilo will connect to the new 4" gate valve installed by others and install new 4" C900 UG pipe into the new building for a fire sprinkler system per NFPA 13R, 2013 and the City of Boise.

(THE DISTRICT AT PARKCENTER - INTOWN BUILDING B - #1) (The drawings are filed under permit BLD14-01818 in ePlanReview) To construct a three story apartment building having a total of 76 dwelling units (24 units 1st story, 26 units 2nd story, and 26 units 3rd story). The 1st story will have a 1,630 square foot storage area with 21 storage units. The interior court on the 1st story will be used for assembly purposes with the egress system passing through the building and sharing the egress system that serves the 1st story apartments. The 1-hr corridors will be enclosed and conditioned and the 1-hr exterior stairways on all stories will be open to the outside. The total floor area of this building is about 81,567 square feet (about 27,189 square feet each story). For building area reasons, this building is divided by a 2-hr fire wall, each side having about 13,550 square feet per story. All ground floor units are required to comply as Type B dwelling units. Because this building does not have an elevator, none of the units located on the 2nd and 3rd stories are regulated for accessibility to the disabled. Work is to include 2-hr fire walls, interior nonbearing walls, 1-hr bearing walls, 1-hr roof-ceiling assemblies, 1-hr floor-ceiling assemblies, 1-hr dwelling unit separations (fire partitions and horizontal assemblies), attic insulation, interior doors, exterior windows and doors, insulated exterior walls, “Hardi-board” exterior siding, exterior manufactured stone wainscot, composition roof shingles, membrane roof coverings for flat roofs, 1-hr common corridors, 1-hr common exterior stairways, draftstops in floors and attics, millwork, and finishes. Structural work includes concrete footings, concrete stem walls, concrete floor slabs on grade with thickened footings at interior bearing walls, wood floor trusses, wood roof trusses, wood columns, wood beams, and shear walls. Special inspection is required for soils, concrete, and wood. The designs for the roof trusses and floor trusses are deferred submittal items. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13R and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/30/20171/30/20171/30/2017APASS
DetailsJim Page
Final fire sprinkler inspection is complete
INSP-Final Inspection9/11/20169/11/20169/11/2016PPASS
DetailsJim Page
INSP-Sprinkler Rough-in/Hydro10/16/201510/16/201510/16/2015PCANC
DetailsJim Page
Please schedule inspection for 4pm. Bryan in the contact. Thanks. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in9/10/20159/10/20159/11/2015PPASS
DetailsJim Page
Underground inspection passed/complete, approved for cover
INSP-Sprinkler Rough-in9/2/20159/2/20159/2/2015PPART
DetailsJim Page
Partial Piping for building installed, piping that is installed approved for cover, still needs tie in to water supply, will be scheduled for inspection at later date for completion of cover inspection.
Permit Ready to Issue  6/8/2015 DONE
Issue and Print Permit  6/8/2015 DONE
Inspection Record Card- Fire6/8/2015 6/8/2015 DONE
DetailsBrittany Hill
Intake Approval  6/2/2015 PASS
Plan assigned to (Tim)6/2/2015 6/2/2015 DONE
DetailsTim Frost
Sprinkler Plan Check6/2/2015 6/2/2015 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  6/2/2015 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  6/2/2015 DONE
DetailsTim Frost
Application received  5/31/2015 DONE
Application submitted via PDS Online on May 31 2015 6:42PM