INSP-Final Inspection | 7/30/2015 | 7/31/2015 | 7/31/2015 | A | PASS |
Jim Page
|
|
|
Previously noted items corrected, fire alarm inspection passed/complete
|
Miscellaneous action | | | 7/29/2015 | | DONE |
|
|
|
Kenny Leslie emailed to ask if as built drawings are acceptable or if a resubmittal would be required for the removal of non required devices and the addition of a duct detector. I responded to say as built drawings would be acceptable.
|
INSP-Final Inspection | 7/27/2015 | 7/28/2015 | 7/28/2015 | P | FAIL |
Troy Cobbley
|
|
|
Missing part of the city approved plans, on ceiling mounted strobe was overspace on the upper level, missing document box. The single strobe in the basement is overspaced and will not provide coverage in a pocket at the bottom of the stairs and in the area under the stairs. These two areas are not shown on the plans. Also the ceiling mounted duct work in the basement cuases an obstruction to the smoke detectors due to exceeding 10% of the ceiling height so spacing needs to be adjusted. I spoke to Lee and there is a possibility that the fire alarm system can be deleted from the basement if the contractor chooses not to provide modifications. Permission and as-builts will be needed prior to a final inspection. Also the address is incorrect. No actual testing was performed.
|
Permit Ready to Issue | | | 7/15/2015 | | DONE |
|
|
|
all requirments met
|
Issue and Print Permit | | | 7/15/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/15/2015 | | 7/15/2015 | | DONE |
Kristal Soland
|
|
|
|
Plan resubmittals received | | | 7/14/2015 | | DONE |
|
|
|
|
1st review completed | | | 7/14/2015 | | PASS |
|
|
|
|
Alarm Plan Check | 7/14/2015 | | 7/14/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/14/2015 | | DONE |
|
|
|
Resubmittal approved with review comments. Projectdox updated.
|
Plan assigned to (Lee) | 6/23/2015 | | 6/23/2015 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 6/23/2015 | | FAIL |
|
|
|
|
Miscellaneous action | | | 6/23/2015 | | DONE |
|
|
|
Emailed applicant to inform the of the need to add an emergency voice / alarm system due to occupant load above 30 in Group E.
|
Application received | | | 6/9/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Jun 9 2015 1:07PM
|