Information based on query as of Saturday, June 29, 2024.
Permit Information
Permit NumberFIR15-00425
StatusFinaled
Name MICRON TECHNOLOGY INC FP
Site Address 8000 S FEDERAL WAY
Project NameMicron B 2 / 3
Customer NumberC23941
ePlanReviewNo
Description
Fire Sprinkler System: C23941 B2/B3 Mask Remodel - B2 2nd. Floor - Remove (E) sprinklers and piping to allow for installation of new sprinklers, approximately 15,000sf.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/22/20163/23/20163/23/2016APASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Sprinkler Rough-in/Hydro3/2/20163/2/20163/2/2016PPASS
DetailsJim Page
Hydrostatic test, 2hrs @ 200psi passed/complete for overhead sprinkler piping.
Issue and Print Permit  3/2/2016 DONE
DetailsChristina Prado
Sprinkler Plan Check2/26/2016 2/26/2016 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  2/26/2016 DONE
DetailsTim Frost
Permit Ready to Issue  2/26/2016 DONE
plans are in the fir drawer under M for Micron
Telephone call  2/26/2016 DONE
sent email to Paul that plan mod is ready
Plan assigned to (Tim)1/29/2016 2/26/2016 DONE
DetailsTim Frost
Plan resubmittals received  2/18/2016 DONE
resubmittals recieved 2 sheets #1, permit app, 1 cover sheet, 1 response letter, 2 hydraulic calcs-put in fire cubby
Plan assigned to (Troy)2/4/2016 2/4/2016 DONE
DetailsTim Frost
Sprinkler Plan Check2/4/2016 2/4/2016 FAIL
DetailsTim Frost
Plan Modification Accepted  2/4/2016 DONE
Telephone call  2/4/2016 DONE
emailed Paul that plan review failed and that he can come pick them up
INSP-Sprinkler Rough-in1/18/20161/19/20161/19/2016AFAIL
DetailsTroy Cobbley
I stopped the rough-in inspection due to the installation not matching the approved plans. Branchlines have been added and several of the branchlines are not in the same location as the plans show them. It appears that the upright sprinkler heads have been hydraulically calculated and are shown placed directly on the branchlines. However they are actually installed on 1" armovers which changes the hydraulic calculations. I noted that there are additional fittings on the 4" main and the 2" branchlines. A low point drain will be needed as discussed. Plans will need to be resubmitted with all changes and revised hydraulic calculations.
Issue and Print Permit  1/15/2016 DONE
Plan assigned to (Tim)12/10/2015 1/13/2016 DONE
DetailsTim Frost
Sprinkler Plan Check1/13/2016 1/13/2016 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  1/13/2016 DONE
DetailsTim Frost
Permit Ready to Issue  1/13/2016 DONE
Telephone call  1/13/2016 DONE
emailed Paul to let know the permit is ready
Plan resubmittals received  1/11/2016 DONE
received (2) sets of calculation & plans
Sprinkler Plan Check12/17/2015 12/17/2015 FAIL
DetailsTim Frost
Please, see attached comments.
1st review completed  12/17/2015 FAIL
DetailsTim Frost
Telephone call  12/17/2015 DONE
emailed Paul that the permit failed
Plan assigned to (Scott)  6/11/2015 DONE
DetailsBill Alexander
This permit was created on the web by Paul Marcolina
Application received  6/11/2015 DONE
This permit was created on the web by Paul Marcolina