Permit Information
Permit NumberFIR15-00561
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1173 W UNIVERSITY DR
Project NameBSU Alumni & Friends Center
Customer Number 
ePlanReviewYes
Description
This is a new 4 level building with full fire sprinkler protection per NFPA 13. Semiautomatic class I standpipe with hose valves on intermediate landings.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/3/201610/3/201610/3/2016PPASS
DetailsJim Page
Final fire sprinkler inspection passed/complete.
INSP-Final Inspection9/29/20169/30/20169/30/2016PCANC
DetailsJim Page
Final fire sprinkler inspection will be rescheduled to coincide with tamper switch wiring completion , tamper switches on backflow and fire pump control valve were not in place. Tamper switches were installed while alarm inspection was happening but still need to be wired into the alarm system.
INSP-Sprinkler Rough-in9/13/20169/20/20169/20/2016PDONE
DetailsJim Page
Fire pump start up complete.
INSP-Sprinkler Rough-in8/1/20168/2/20168/2/2016APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping located on level 4 complete, overhead fire sprinkler piping located on level 4 approved for cover. Rough to cover inspection complete for overhead fire sprinkler piping located above the hardlids on level 1, overhead fire sprinkler piping located above the hardlids on level 1 approved for cover
INSP-Sprinkler Rough-in8/1/20168/1/20168/1/2016PCANC
DetailsJim Page
Rough to cover inspection cancelled by point of contact, Mark Jensen ( ###-#### ), rough to cover inspection will be rescheduled for a later date.
INSP-Sprinkler Rough-in7/21/20167/22/20167/22/2016APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping located on level 4 complete, overhead fire sprinkler piping located on level 4 approved for cover. Rough to cover inspection complete for overhead fire sprinkler piping located above the hardlids on level 1, overhead fire sprinkler piping located above the hardlids on level 1 approved for cover.
INSP-Sprinkler Rough-in/Hydro7/6/20167/7/20167/7/2016PPASS
DetailsJim Page
Rough to cover inspection complete for overhead fire sprinkler piping located on levels 2 and 3, overhead fire sprinkler piping on levels 2 and 3 approved for cover.
INSP-Sprinkler Rough-in5/19/20165/20/20165/20/2016APART
DetailsJim Page
Rough to cover inspection complete for hardlids located in the 4th floor stairwell, notated the city approved drawings with yellow highlighter the lines that were inspected. Area's notated with yellow highlighter approved for cover.
INSP-Sprinkler Rough-in5/3/20165/5/20165/5/2016PPART
DetailsJim Page
Notated area's inspected with green highlighter on city approved plans. Area's notated approved for cover.
INSP-Sprinkler Rough-in3/31/20164/1/20164/1/2016PCANC
DetailsJim Page
Inspection request will be rescheduled, discussed reschedule with point of contact, Mark, phone number ###-####. Rough in inspection will be rescheduled for 04APR16.
INSP-Sprinkler Rough-in3/16/20163/16/20163/16/2016PPASS
DetailsJim Page
Rough to cover inspection for elevator equipment on 1st floor complete, elevator equipment room fire sprinkler piping approved for cover. Notated area for cover with red ink on city approved drawings.
Miscellaneous action  10/26/2015 DONE
Email regarding space above stair tower.

Tom,

Per our conversations.

I believe the space at the top of the stair tower meets the intent of the code section below. The space above the stair tower can only be accessed when you climb the far stair tower, go across the roof and enter this space.

A sign shall be provided on the door, indicating the space cannot be occupied or be used for any type of storage. The space shall remain locked at all times. If at a later date the space is found to be in use, fire protection will immediately required.

8.15.1.2.1* Concealed spaces of noncombustible and limited combustible construction with minimal combustible loading
having no access shall not require sprinkler protection.
Permit Ready to Issue  10/15/2015 DONE
Issue and Print Permit  10/15/2015 DONE
Inspection Record Card- Fire10/15/2015 10/15/2015 DONE
DetailsChristina Prado
Sprinkler Plan Check10/12/2015 10/12/2015 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  10/12/2015 DONE
DetailsTim Frost
Sprinkler Plan Check10/9/2015 10/9/2015 FAIL
DetailsTim Frost
Sprinkler Plan Check9/30/2015 9/30/2015 FAIL
DetailsTim Frost
Sprinkler Plan Check8/26/2015 8/26/2015 FAIL
DetailsTim Frost
1st review completed  8/26/2015 FAIL
DetailsTim Frost
Miscellaneous action  8/26/2015 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Intake Approval  8/25/2015 PASS
Plan assigned to (Tim)8/25/2015 8/25/2015 DONE
DetailsTim Frost
Application received  8/10/2015 DONE
Application submitted via PDS Online on Aug 10 2015 11:11AM