Permit Information
Permit NumberFIR15-00618
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 12301 W EXPLORER DR
Project NameSyringa Networks Fire Alarm
Customer Number 
ePlanReviewYes
Description
Replace existing fire panel with a non-proprietary Silent Knight panel. Replace all existing addressable devices, the existing NAC devices and NAC booster are to be removed. They are not required by code. This permit also includes monitoring of two new duct detectors and the new clean agent suppression system in the current Syrings Networks C0-Locate T.I. This permit does not include the future T.I.'s for the vacant spaces or other future T.I.'s for Syringa Networks. This permit is only to replace the existing fire panel and addressable devices. This work is not associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/29/20163/1/20163/1/2016APASS
DetailsTroy Cobbley
Permit finaled
Telephone call  2/25/2016 DONE
Karrie Donato of Syringa called to say that the fire alarm contractor removed horns & strobes. Syringa had been installing horns and strobes over the past 3 years (with permits) in an effort to provide full notification, although it was not required. During review of this project, it was noted that existing notification did not meet current code so I informed the contractor to provide full coverage or remove non required devices. The contractor elected to remove instead of add. Karrie indicated that their plan was to add full notification through planned tenant improvements. I informed her that this would require an upgrade agreement with fire and building officials.
Miscellaneous action  2/25/2016  
This site was acquired by Syringa Networks in 2013. During seperate tenant improvements of individual / non contigsous spaces between then and 2016, non require audible and visible notification was permitted and installed with the owners intent of having full notification throughout. Through this project (full system replacement) it was noted in review comments that some areas did not have adequate visible coverage. Option was given to provide full coverage or remove non require devices. Contractor removed non required devices. This was not the owners intent, as noted above. Owner plans to add full notification back in and was informed that an upgrade agreement would be required if this is to be done over a period of time. Otherwise, full notification could be added under 1 permit or it could be left as is.
INSP-Final Inspection2/23/20162/24/20162/24/2016PFAIL
DetailsTroy Cobbley
Will be ok to final when the SImplex permit for the dialer is finaled.
INSP-Final Inspection1/31/20162/1/20162/1/2016PFAIL
DetailsTroy Cobbley
See the city approved drawings for list of correctins needed for a final
INSP-Final Inspection1/28/20161/29/20161/28/2016PCANC
DetailsTroy Cobbley
Have appointment in the morning, free after 10:00 all day. Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
INSP-Final Inspection1/26/20161/27/20161/28/2016PCANC
DetailsTroy Cobbley
Phone #: ###-#### Inspection requested via web by Brian Richard
INSP-Final Inspection1/25/20161/26/20161/26/2016PCANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
INSP-Alarm Testing12/17/201512/24/201512/24/2015ADONE
DetailsJim Page
Notated devices tested on city approved drawings.
INSP-Alarm Testing12/17/201512/23/201512/23/2015ADONE
DetailsJim Page
Notated devices tested/passed on city approved drawings.
INSP-Alarm Testing12/18/201512/22/201512/22/2015PDONE
DetailsTroy Cobbley
See the city approved plans for corridor detectors tested today. The fire doors did not release upon alarm of the corridor detectors, water flow switch did not function, elevator hat did not function. We tried to test some duct smoke detectors but the units would not turn on.
INSP-Alarm Testing12/14/201512/21/201512/21/2015PDONE
DetailsTroy Cobbley
As-builts are needed showing deleted devices, added devices and address changes. Verified battery size in panel and panel model. Verifed a/v's have been removed per the approved plans. I noted that the smoke detectors for door release will need to be centered on doors. The access controled egress doors will need to be connected to the fire alarm system per the IFC. Interior doors on hold opens need to release on alarm and when the panel becomes inactive as discussed.
INSP-Alarm Testing12/17/201512/22/201512/18/2015ACANC
DetailsTroy Cobbley
>> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
INSP-Alarm Testing12/14/201512/16/201512/14/2015PCANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
INSP-Alarm Testing12/14/201512/17/201512/14/2015PCANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
INSP-Alarm Testing12/14/201512/18/201512/14/2015ACANC
DetailsTroy Cobbley
following and during clean agent inspection FIR15-00513 Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
INSP-Sprinkler Rough-in/Hydro12/14/201512/18/201512/14/2015PCANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
Permit Ready to Issue  9/30/2015 DONE
Issue and Print Permit  9/30/2015 DONE
Inspection Record Card- Fire9/30/2015 9/30/2015 DONE
DetailsChristina Prado
Alarm Plan Check9/29/2015 9/29/2015 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  9/29/2015 DONE
Plans approved with review comments.
Plan resubmittals received  9/24/2015 DONE
Revised plans received. Non required notification removed.
Plan assigned to (Lee)9/2/2015 9/2/2015 DONE
DetailsLee G Meredith
1st review completed  9/2/2015 FAIL
Missing room names, ceiling heights, scale reference, notification incorrect and in general, does not meet current code requirements.
Miscellaneous action  9/2/2015 DONE
Notified applicant through eplanreview email that the submittal was failed for reasons noted in the email.
Application received  8/31/2015 DONE
Application submitted via PDS Online on Aug 31 2015 10:35PM