INSP-Final Inspection | 11/2/2016 | 11/2/2016 | 11/2/2016 | P | PASS |
Katie Marron
|
|
|
Verified central monitoring station receiving signals, tested a trouble, alarm and supervisory.
Scope of work complete, permit finaled.
|
INSP-Final Inspection | 10/26/2016 | 10/28/2016 | 10/28/2016 | P | FAIL |
Jim Page
|
|
|
All devices tested on fire alarm system, only item left is to verify monitoring, phone lines did not have dial tone at time of inspection.
|
Telephone call | | | 9/8/2016 | | DONE |
|
|
|
Morgan called to say that a smoke detector was being added in the elevator shaft for damper control. Wanted to know if resubmittal was required. Informed him to provide revised drawings for as built archives. Resubmittal not needed.
|
1st review completed | | | 9/17/2015 | | PASS |
|
|
|
|
Alarm Plan Check | 9/17/2015 | | 9/17/2015 | | PASS |
Lee G Meredith
|
|
|
As Noted
|
PLANS TAKEN FRONT DESK ALARM | | | 9/17/2015 | | DONE |
|
|
|
Plans approved with review comments and requirements.
|
Permit Ready to Issue | | | 9/17/2015 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/17/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/17/2015 | | 9/17/2015 | | DONE |
Candy A. Nichols
|
|
|
|
Application received | | | 9/16/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 16 2015 10:31AM
|
Plan assigned to (Lee) | 9/16/2015 | | 9/16/2015 | | DONE |
Lee G Meredith
|
|
|
|