INSP-Final Inspection | 11/15/2016 | 11/15/2016 | 11/15/2016 | A | PASS |
Jim Page
|
|
|
Pemit finaled
|
INSP-Final Inspection | 11/14/2016 | 11/14/2016 | 11/14/2016 | P | PASS |
Jim Page
|
|
|
Final Fire Sprinkler Inspection complete.
|
INSP-Final Inspection | 10/31/2016 | 11/1/2016 | 11/1/2016 | A | PART |
Troy Cobbley
|
|
|
Vertical sidewall heads have been added at the windows. I have had discussions with Scott about the requested final for this project and it has been determined that when the required signage is provided at all of the FDC's then a final on this permit can be given.
|
INSP-Final Inspection | 10/31/2016 | 10/31/2016 | 10/31/2016 | P | FAIL |
Troy Cobbley
|
|
|
The two new window sprinklers are not installed as per the installation guide for distance below the window mullion. Also before a final sign off the signage the describes the area serviced by the FDC's need to be installed. Scott and I discussed final sign offs.
|
INSP-Final Inspection | 9/20/2016 | 9/21/2016 | 9/21/2016 | A | PART |
Jim Page
|
|
|
Partial final for convention center fire sprinkler systems, area's complete are level 5, level 4, level 2 and level 1 lobby. Dry systems for level 3 and level 2 complete and in service. Level 1 fire sprinkler system will be inspected (excluding level 1 elevator lobby, sprinklers for this area complete)
|
INSP-Final Inspection | 9/13/2016 | 9/20/2016 | 9/20/2016 | P | CANC |
Jim Page
|
|
|
Inspection request will be completed on 21SEPT2016, this inspection request cancelled and new inspection request coordinated with job site foreman.
|
INSP-Final Inspection | 9/19/2016 | 9/19/2016 | 9/19/2016 | P | PART |
Jim Page
|
|
|
Partial final inspection complete for fire sprinklers, levels 4, 5 and 2 wet systems, complete for tampers, flow switch and final overhead fire sprinkler inspection. Level 3 dry system inspection complete, 2nd floor dry system will be completed at a later date.
|
INSP-Sprinkler Rough-in/Hydro | 9/13/2016 | 9/19/2016 | 9/19/2016 | P | CANC |
Jim Page
|
|
|
No inspection request needed for today per conversation with Mike, phone number ###-####, this inspection request is cancelled.
|
Miscellaneous action | | | 9/19/2016 | | DONE |
|
|
|
The FD training said they stage on the landing. Therefore, a roof standpipe outlet is not required.
|
Plan Modification Accepted | | | 9/19/2016 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 9/19/2016 | | 9/19/2016 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 9/19/2016 | | 9/19/2016 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/19/2016 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 9/19/2016 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 9/16/2016 | 9/16/2016 | 9/16/2016 | P | PASS |
Jim Page
|
|
|
Hydrostatic test complete for wet pipe? fire sprinkler systems located on levels 2 and 4 (Area labeled level 5 is off of the level 4 wet system) Standpipe hydrostatic test for district/convention center complete.
|
INSP-Sprinkler Rough-in | 9/9/2016 | 9/16/2016 | 9/16/2016 | P | PASS |
Jim Page
|
|
|
24 hour air test complete for level 2 and level 3 dry systems protecting parking garages. 200psi hydrostatic test complete for parking garage dry systems (level 2 and 3)
|
INSP-Sprinkler Rough-in | 9/9/2016 | 9/15/2016 | 9/15/2016 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping located in the soffits and above ceiling grid area's on level 2 of the convention center complete, overhead fire sprinkler piping located above soffits and ceiling grid area's on level 2 approved for cover.
|
INSP-Sprinkler Rough-in | 9/9/2016 | 9/14/2016 | 9/14/2016 | P | CANC |
Jim Page
|
|
|
Inspection request for VRT, FIR16-00265. This inspection request cancelled and a new inspection request will be generated.
|
INSP-Sprinkler Rough-in | 9/9/2016 | 9/13/2016 | 9/13/2016 | P | CANC |
Jim Page
|
|
|
Inspection request will be performed on 14SEPT2016.
|
INSP-Sprinkler Rough-in/Hydro | 9/13/2016 | 9/20/2016 | 9/13/2016 | P | CANC |
Jim Page
|
|
|
Please schedule this final inspection for Convention Center. If you have questions please call Mike Martin at ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Kay Haney Inspection cancelled from web by: Kay Haney
|
INSP-Sprinkler Rough-in | 9/9/2016 | 9/12/2016 | 9/12/2016 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection complete for overhead fire sprinkler piping located above the convention center level 2 soffits & hardlids, level 4 ceiling grid area's & hardlids, level 3 dry stsem as well as level 2 dry system, area's inspected for rough to cover inspection approved for cover.
|
INSP-Sprinkler Rough-in/Hydro | 9/9/2016 | 9/12/2016 | 9/9/2016 | P | CANC |
Jim Page
|
|
|
Mike Martin is the contact for this inspection. He wanting a rough to cover inspection. Phone #: ###-#### >> Inspection requested via web by Kay Haney Inspection cancelled from web by: Kay Haney
|
INSP-Sprinkler Rough-in | 8/25/2016 | 8/25/2016 | 8/25/2016 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping in the ballroom, sections B and C complete. Overhead fire sprinkler piping located above the grid ceiling in ballroom approved for cover.
|
INSP-Sprinkler Rough-in | 8/23/2016 | 8/23/2016 | 8/23/2016 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping located above the ceiling grid in ballroom Section A complete, overhead fire sprinkler in ballroom Section A approved for cover. Rough to cover inspection for overhead fire sprinkler piping located in level 4 escalator lobby complete, overhead fire sprinkler piping located above the hardlids on level 4 escalator lobby approved for cover.
|
INSP-Sprinkler Rough-in/Hydro | 8/16/2016 | 8/16/2016 | 8/16/2016 | P | CANC |
Jim Page
|
|
|
Hydrostatic test will be reschedule for later date.
|
INSP-Sprinkler Rough-in/Hydro | 8/15/2016 | 8/15/2016 | 8/15/2016 | P | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping above restrooms in the commercial kitchen area complete, overhead piping above restroom hardlids in commercial kitchen approved for cover. Rough to cover inspection for overhead fire sprinkler piping located above the soffits on level 4 complete, overhead fire sprinkler piping located above level 4 soffits approved for cover. Rough in inspections for level 1 wet system complete, level 3 wet system complete, level 2 dry system complete as well as stairwells.
|
INSP-Sprinkler Rough-in/Hydro | 8/11/2016 | 8/12/2016 | 8/11/2016 | P | CANC |
Jim Page
|
|
|
Inspection request rescheduled by me for 15AUG2016 per conversation with point of contact, Mike phone ###-####.
|
INSP-Sprinkler Rough-in | 8/11/2016 | 8/12/2016 | 8/11/2016 | P | CANC |
Jim Page
|
|
|
Inspection request rescheduled by me for 15AUG2016 per conversation with point of contact, Mike phone ###-####.
|
INSP-Final Inspection | 7/26/2016 | 7/27/2016 | 7/27/2016 | A | CANC |
Jim Page
|
|
|
Inspection request cancelled per conversation with point of contact, Mike phone number ###-####.
|
Plan Modification Accepted | | | 3/3/2016 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 3/3/2016 | | 3/3/2016 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/3/2016 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 3/3/2016 | | DONE |
|
|
|
|
Sprinkler Plan Check | 12/22/2015 | | 12/22/2015 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
Sprinkler Plan Check | 12/22/2015 | | 12/22/2015 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/22/2015 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 12/22/2015 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/22/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/22/2015 | | 12/22/2015 | | DONE |
Christina Prado
|
|
|
|
Sprinkler Plan Check | 12/2/2015 | | 12/2/2015 | | FAIL |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 11/19/2015 | | 11/19/2015 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 11/19/2015 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Intake Approval | | | 10/27/2015 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 10/27/2015 | | 10/27/2015 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 10/27/2015 | | 10/27/2015 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 10/27/2015 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 10/27/2015 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Intake Approval | | | 10/26/2015 | | PASS |
|
|
|
|
Sprinkler Plan Check | 10/26/2015 | | 10/26/2015 | | DONE |
Tim Frost
|
|
|
|
Application received | | | 10/16/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Oct 16 2015 9:54AM
|