Case Summary | | | 6/6/2016 | | DONE |
|
|
|
|
INSP-Final Inspection | 1/27/2016 | 1/28/2016 | 1/28/2016 | A | PASS |
Jim Page
|
|
|
Fire alarm inspection passed/complete for new fire panel/annunciator, existing upgraded smoke detectors and heat detectors, elevator recall as well as fire sprinkler components.
|
INSP-Final Inspection | 1/26/2016 | 1/27/2016 | 1/27/2016 | A | CANC |
Jim Page
|
|
|
Inspection request cancelled per conversation with, Josh Phone #: ###-####, will reschedule for later date.
|
Alarm Plan Check | 1/26/2016 | | 1/26/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/26/2016 | | DONE |
|
|
|
Plan modification approved.
|
CHANGE STATUS TO (ISS) | | | 1/26/2016 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/25/2016 | | DONE |
|
|
|
Resubmittal of plan modification received
|
Miscellaneous action | | | 1/22/2016 | | DONE |
|
|
|
Emailed Josh Bess to inform him that I have failed this resubmittal on prescreen review due to the lack of information provided on the resubmittal. I let him know that I need to know which smoke detector locations have changed and which model is installed at a given location.
|
CHANGE STATUS TO (REV) | | | 1/22/2016 | | DONE |
|
|
|
Permit was previously issued. Changed to REV for plan modification. Reviewed and failed due to lack of information.
|
Plan resubmittals received | | | 1/21/2016 | | DONE |
|
|
|
Plan mod received for smoke detector model changes.
|
Permit Ready to Issue | | | 11/5/2015 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/5/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/5/2015 | | 11/5/2015 | | DONE |
Kristal Soland
|
|
|
|
Miscellaneous action | | | 11/4/2015 | | DONE |
|
|
|
Revisions provided.
|
1st review completed | | | 11/4/2015 | | PASS |
|
|
|
|
Alarm Plan Check | 11/4/2015 | | 11/4/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/4/2015 | | DONE |
|
|
|
Plans approved as noted, with review comments.
|
Miscellaneous action | | | 10/27/2015 | | DONE |
|
|
|
Emailed Josh Bess requesting notification power supply calculations.
|
Miscellaneous action | | | 10/26/2015 | | DONE |
|
|
|
Corrected drawings received and inserted into projectdox.
|
Miscellaneous action | | | 10/23/2015 | | DONE |
|
|
|
Emailed applicant with a request for room identification to be noted per 2012 IFC 907.1.2(1). He responded to indicate new drawings would be provided on Monday 10/26/15 with the requested information.
|
Plan assigned to (Lee) | 10/23/2015 | | 10/23/2015 | | DONE |
Lee G Meredith
|
|
|
|
Application received | | | 10/16/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Oct 16 2015 2:50PM
|