INSP-Final Inspection | 6/9/2016 | 6/9/2016 | 6/9/2016 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection passed/complete
|
INSP-Final Inspection | 6/2/2016 | 6/2/2016 | 6/2/2016 | A | PART |
Jim Page
|
|
|
Inspected pull stations, smoke detectors and A/V's in office area's, battery room, electrical room and fire sprinkler riser room, all tested correctly. Inspected tamper switches, flow switches and low air alarm. Outside bell did not ring with dry system water flow or south side wet system water flow, items will be corrected and reinspected at next inspection request.
|
INSP-Final Inspection | 5/31/2016 | 5/31/2016 | 5/31/2016 | A | PART |
Jim Page
|
|
|
Tested/Inspected duct detectors/HVAC unit shutdown, second level clean mech room as well as second level dirty mech room, all devices tested today operated correctly and provided unti shutdown for HVAC units.
|
INSP-Final Inspection | 5/25/2016 | 5/25/2016 | 5/25/2016 | A | PART |
Jim Page
|
|
|
Inspected audio visual devices for firest floor clean room as well as second level clean and dirty mech room. Devices tested today passed/complete.
|
INSP-Final Inspection | 5/24/2016 | 5/24/2016 | 5/24/2016 | A | CANC |
Jim Page
|
|
|
Inspection request cancelled per conversation with Jeff, inspection request will be rescheduled for the following day.
|
Plan Modification Accepted | | | 5/19/2016 | | DONE |
|
|
|
|
Alarm Plan Check | 5/19/2016 | | 5/19/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 5/19/2016 | | DONE |
|
|
|
On site plan modification review approved with minor redline comments on notification coverage.
|
Permit Ready to Issue | | | 5/19/2016 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 5/19/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/24/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/24/2015 | | 11/24/2015 | | DONE |
Brittany Hill
|
|
|
|
Permit Ready to Issue | | | 11/20/2015 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 11/9/2015 | | 11/19/2015 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 11/19/2015 | | PASS |
|
|
|
|
Alarm Plan Check | 11/19/2015 | | 11/19/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/19/2015 | | DONE |
|
|
|
Plans approved as noted. No written review comments.
|
Application received | | | 10/22/2015 | | DONE |
Mary Froemke
|
|
|
This permit was created on the web by Paul Marcolina
|
Application received | | | 10/22/2015 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|