Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR15-00770
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 505 E PARKCENTER BLVD
Project NameDistrict @ Parkcenter Cottage
Customer Number 
ePlanReviewYes
Description
[The District at Park Center - Cottage Building A-#3]
The fire sprinkler scope of work consists of protecting a two level apartment building per NFPA 13R. The system is supplied by 4”x60’ ± C-900 underground piping. Extended coverage residential sprinklers and CPVC piping are being utilized.

(THE DISTRICT AT PARKCENTER - COTTAGE BUILDING A - #3) (The drawings are filed under permit BLD14-01818 in ePlanReview) To construct a 10 dwelling unit two story apartment building with each unit having its own garage (i.e. 10 garages). The total floor area of this building is about 14,708 square feet (8,374 square feet 1st story and 6,334 square feet 2nd story). All ground floor units are required to comply as Type B units. Two of those ground floor units within Cottage Building A - #2 are required to comply as Type A units. Work is to include interior nonbearing walls, 1-hr bearing walls, 1-hr roof-ceiling assemblies, 1-hr floor-ceiling assemblies, 1-hr dwelling unit separations, attic insulation, interior doors, exterior windows and doors, insulated exterior walls, “Hardi-board” exterior siding, exterior manufactured stone wainscot, composition roof shingles, common stairways within a 1-hr corridor, private interior stairways, garages, garage overhead doors, millwork, and finishes. Structural work includes concrete footings, concrete stem walls, concrete floor slabs on grade with thickened footings at interior bearing walls, wood floor trusses, wood roof trusses, wood columns, wood beams, and shear walls. Special inspection is required for soils, concrete, and wood. The designs for the roof trusses and floor trusses are deferred submittal items. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13R as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/30/20168/31/20168/31/2016APASS
DetailsJim Page
Final fire alarm inspection passed/complete
INSP-Sprinkler Rough-in4/22/20164/22/20164/22/2016PPASS
DetailsJim Page
Rough to cover inspection complete, tenting inspection complete, all overhead fire sprinkler piping approved for cover.
INSP-Conference4/22/20164/22/20164/22/2016PCANC
DetailsJim Page
Inspection request for rough to cover, not a conference. This request cancelled and a rough to cover request will be generated.
INSP-Sprinkler Rough-in4/20/20164/20/20164/20/2016PPART
DetailsJim Page
Rough to cover inspection complete for entire building, 1st floor piping that is not in attic spaces approved for cover. 2nd level/attic (1st floor garages, garage stairways) space fire sprinkler piping rough to cover inspection complete, these area's cannot be covered until tenting inspection is completed and approved.
INSP-Sprinkler Rough-in/Hydro4/20/20164/20/20164/20/2016PPASS
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping complete for 1st and 2nd levels.
Plan assigned to (Tim)4/19/2016 4/19/2016 DONE
DetailsTim Frost
Plan Modification Accepted  4/19/2016 DONE
Sprinkler Plan Check4/19/2016 4/19/2016 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  4/19/2016 DONE
DetailsTim Frost
(F) Reprint permit  4/19/2016 DONE
CHANGE STATUS TO (ISS)  4/19/2016 DONE
Plan Mod
INSP-Sprinkler Rough-in4/11/20164/11/20164/11/2016PFAIL
DetailsTroy Cobbley
Plan Modifications Are Required. Could not perform/finish rough-in since not all of the r/c's (pendant heads) had been installed. I found a missing head in the second floor remote area. There are extensive pipe changes which includes routing and many additional fittings including changing from the approved sidewall heads to pendant heads in the garage areas. Patio sidewall heads have been re-routed. Hangers are missing and heads are overspaced. Some heads can't provide coverage due to shadowing caused by walls (instead of installing two heads as per the plans, the fitter is trying to use one head to provide coverage). No tenting has been installed yet. The Fire Dept Connection was in the process of being installed in another location that was not shown on the approved plans.
INSP-Sprinkler Rough-in/Hydro4/11/20164/11/20164/11/2016PFAIL
DetailsTroy Cobbley
Could not perform hydro since not all of the r/c's (pendant heads) had been installed. I found a missing head in the second floor remote area. There are extensive pipe changes which includes routing and many additional fittings including changing from the approved sidewall heads to pendant heads in the garage areas.
Permit Ready to Issue  11/6/2015 DONE
all requirments met
Issue and Print Permit  11/6/2015 DONE
Inspection Record Card- Fire11/6/2015 11/6/2015 DONE
DetailsCarlos Velazquez
Sprinkler Plan Check11/4/2015 11/4/2015 PASS
DetailsTim Frost
Please, see attached comments.
1st review completed  11/4/2015 PASS
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  11/4/2015 DONE
DetailsTim Frost
Intake Approval  11/3/2015 PASS
Plan assigned to (Tim)11/3/2015 11/3/2015 DONE
DetailsTim Frost
Application received  10/30/2015 DONE
Application submitted via PDS Online on Oct 30 2015 2:00PM