INSP-Final Inspection | 5/25/2016 | 5/26/2016 | 5/26/2016 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection passed/complete.
|
INSP-Alarm Testing | 5/24/2016 | 5/25/2016 | 5/25/2016 | P | CANC |
Troy Cobbley
|
|
|
Overbooked. Rescheduled for tomorrow morning.
|
CHANGE STATUS TO (ISS) | | | 4/6/2016 | | DONE |
|
|
|
plan mod fees paid
|
Plan resubmittals received | | | 4/5/2016 | | DONE |
|
|
|
|
Alarm Plan Check | 4/5/2016 | | 4/5/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 4/5/2016 | | DONE |
|
|
|
Plan modification approved.
|
Miscellaneous action | | | 4/4/2016 | | DONE |
|
|
|
Mary emailed a request to have the project workflow opened so she can upload a plan modification.
|
INSP-Final Inspection | 3/2/2016 | 3/3/2016 | 3/3/2016 | A | PART |
Troy Cobbley
|
|
|
Fire alarm is complete in the South tenant space of the building. As-builts need submitted showing the correct device addresses and the new strobe.
|
Plan Modification Accepted | | | 3/2/2016 | | DONE |
|
|
|
|
CHANGE STATUS TO (REV) | | | 3/2/2016 | | DONE |
|
|
|
Plan modification in review
|
Alarm Plan Check | 3/2/2016 | | 3/2/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 3/2/2016 | | DONE |
|
|
|
Plan modification approved as noted on drawings. No additional review comments.
|
Miscellaneous action | | | 3/2/2016 | | DONE |
|
|
|
Emailed Paula to inform her that smokes were still shown ing the toilet / showers. Informed her that these were not allowed, as noted on previous review. Fixed heats can be substituted if detectors are needed.
|
CHANGE STATUS TO (ISS) | | | 3/2/2016 | | DONE |
Christina Prado
|
|
|
|
INSP-Final Inspection | 2/24/2016 | 2/25/2016 | 2/25/2016 | P | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for locations of corrections needed on the horn strobe circuits This includes an add and candella changes. The beam detector at the south end of building has been deleted so spot type detectors will need to be placed. Horns did not sync.The smoke detector in the riser room is mislabeled as water flow. The manual pull stations tested ok. None of the devices in the north half of the building have been installed yet.
|
Telephone call | | | 2/25/2016 | | DONE |
|
|
|
Troy Cobbley called to discuss smoke detector requirements in corridors to waiting areas. I informed him that due to the occupancy, they were required and that I was not able to find a code that required additional detection when the corridor was open to the ceiling. That is to say, detectors will be allowed on the open ceiling above these corridors.
|
Permit Ready to Issue | | | 12/3/2015 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/3/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/3/2015 | | 12/3/2015 | | DONE |
Kristal Soland
|
|
|
|
Alarm Plan Check | 12/2/2015 | | 12/2/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 12/2/2015 | | DONE |
|
|
|
Resubmittal approved with review comments.
|
Plan resubmittals received | | | 12/1/2015 | | DONE |
|
|
|
|
Telephone call | | | 11/20/2015 | | DONE |
|
|
|
Mary called to discuss smoke detection in corridor requirements noted in review comments. We agreed that they would need to be added in corridors 2 and 3 to meet 2012 IFC 907.2.6.1 exception 1 pertaining to corridors and waiting rooms open to corridors. Corridor 5 will not require smokes. She will contact the architect to see if he wants to add a door to eliminate detection in corridor from day room 130 to reception 101.
|
Miscellaneous action | | | 11/16/2015 | | DONE |
|
|
|
Mary Froemke seemed to question corridor detection requirements. I responded to indicate the requirements of 907.2.6.1 which includes smoke detection in all corridors and waiting areas open to corridors. I also provided IFC definitions to habitable space and corridors.
|
Plan assigned to (Lee) | 11/13/2015 | | 11/13/2015 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 11/13/2015 | | FAIL |
|
|
|
See 1st review comments.
|
Miscellaneous action | | | 11/13/2015 | | DONE |
|
|
|
Emailed applicant and designer 1st failed review comments.
|
Application received | | | 11/12/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Nov 12 2015 1:33PM
|