Permit Information
Permit NumberFIR15-00807
StatusFinaled
Name ALARM STAR
Site Address 7360 W BETHEL ST
Project NamePort of Hope
Customer Number 
ePlanReviewYes
Description
Alter and Extend the existing fire sprinkler monitoring system into a complete manual fire alarm system. Associated with building permit BLD15-02842.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/25/20165/26/20165/26/2016APASS
DetailsJim Page
Final fire alarm inspection passed/complete.
INSP-Alarm Testing5/24/20165/25/20165/25/2016PCANC
DetailsTroy Cobbley
Overbooked. Rescheduled for tomorrow morning.
CHANGE STATUS TO (ISS)  4/6/2016 DONE
plan mod fees paid
Plan resubmittals received  4/5/2016 DONE
Alarm Plan Check4/5/2016 4/5/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  4/5/2016 DONE
Plan modification approved.
Miscellaneous action  4/4/2016 DONE
Mary emailed a request to have the project workflow opened so she can upload a plan modification.
INSP-Final Inspection3/2/20163/3/20163/3/2016APART
DetailsTroy Cobbley
Fire alarm is complete in the South tenant space of the building. As-builts need submitted showing the correct device addresses and the new strobe.
Plan Modification Accepted  3/2/2016 DONE
CHANGE STATUS TO (REV)  3/2/2016 DONE
Plan modification in review
Alarm Plan Check3/2/2016 3/2/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  3/2/2016 DONE
Plan modification approved as noted on drawings. No additional review comments.
Miscellaneous action  3/2/2016 DONE
Emailed Paula to inform her that smokes were still shown ing the toilet / showers. Informed her that these were not allowed, as noted on previous review. Fixed heats can be substituted if detectors are needed.
CHANGE STATUS TO (ISS)  3/2/2016 DONE
DetailsChristina Prado
INSP-Final Inspection2/24/20162/25/20162/25/2016PFAIL
DetailsTroy Cobbley
See the city approved plans for locations of corrections needed on the horn strobe circuits This includes an add and candella changes. The beam detector at the south end of building has been deleted so spot type detectors will need to be placed. Horns did not sync.The smoke detector in the riser room is mislabeled as water flow. The manual pull stations tested ok. None of the devices in the north half of the building have been installed yet.
Telephone call  2/25/2016 DONE
Troy Cobbley called to discuss smoke detector requirements in corridors to waiting areas. I informed him that due to the occupancy, they were required and that I was not able to find a code that required additional detection when the corridor was open to the ceiling. That is to say, detectors will be allowed on the open ceiling above these corridors.
Permit Ready to Issue  12/3/2015 DONE
Issue and Print Permit  12/3/2015 DONE
Inspection Record Card- Fire12/3/2015 12/3/2015 DONE
DetailsKristal Soland
Alarm Plan Check12/2/2015 12/2/2015 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/2/2015 DONE
Resubmittal approved with review comments.
Plan resubmittals received  12/1/2015 DONE
Telephone call  11/20/2015 DONE
Mary called to discuss smoke detection in corridor requirements noted in review comments. We agreed that they would need to be added in corridors 2 and 3 to meet 2012 IFC 907.2.6.1 exception 1 pertaining to corridors and waiting rooms open to corridors. Corridor 5 will not require smokes. She will contact the architect to see if he wants to add a door to eliminate detection in corridor from day room 130 to reception 101.
Miscellaneous action  11/16/2015 DONE
Mary Froemke seemed to question corridor detection requirements. I responded to indicate the requirements of 907.2.6.1 which includes smoke detection in all corridors and waiting areas open to corridors. I also provided IFC definitions to habitable space and corridors.
Plan assigned to (Lee)11/13/2015 11/13/2015 DONE
DetailsLee G Meredith
1st review completed  11/13/2015 FAIL
See 1st review comments.
Miscellaneous action  11/13/2015 DONE
Emailed applicant and designer 1st failed review comments.
Application received  11/12/2015 DONE
Application submitted via PDS Online on Nov 12 2015 1:33PM