Permit Information
Permit NumberFIR15-00824
StatusFinaled
Name TAYLOR BROTHERS FIRE & SAFETY INC
Site Address 2001 E AMITY RD
Project NameFM-200 Suppression Install
Customer Number 
ePlanReviewYes
Description
Replacement of old Halon suppression system and installation of a new FM-200 clean agent suppression system. System will be installed per NFPA 2001 and manufacturers specifications. Drawings and control calculations has been performed by Fundamental Alarm Designs LLC and the suppression system components have been designed by Taylor Brothers Fire & Safety per manufacturers specification.

There does not seem to be an associated building permit at this time.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/21/201512/22/201512/22/2015PPASS
DetailsJim Page
Final alarm/suppression system inspection passed/complete
Miscellaneous action  11/23/2015 DONE
Fire alarm review by Lee Meredith, suppression system review by Tim Frost.
1st review completed  11/23/2015 PASS
Alarm Plan Check11/23/2015 11/23/2015 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  11/23/2015 DONE
Plans approved with review comments for fire alarm and suppression.
Permit Ready to Issue  11/23/2015 DONE
Issue and Print Permit  11/23/2015 DONE
Inspection Record Card- Fire11/23/2015 11/23/2015 DONE
DetailsCandy A. Nichols
Plan assigned to (Lee)11/19/2015 11/19/2015 DONE
DetailsLee G Meredith
Miscellaneous action  11/19/2015 DONE
Submittal failed prescreen review. No graphic scale provided. Also, the manual activation needs to be located outside of the protected area. Jordan Taylor was notified via email.
Application received  11/18/2015 DONE
Application submitted via PDS Online on Nov 18 2015 1:57PM