INSP-Final Inspection | 8/18/2016 | 8/18/2016 | 8/18/2016 | P | PASS |
Jim Page
|
|
|
Previously noted items have been repaired, ceiling fans that were located to close to smoke detectors have been removed and covers installed over electrical boxes at time of inspection. Flow switch, backlow tamper switches and post indicator valve on fire sprinkler system all tested correctly. Batteries were changed to 7 amp hour batteries to coincide with city approved drawings. Final fire alarm inspection passed/complete.
|
INSP-Final Inspection | 8/8/2016 | 8/8/2016 | 8/8/2016 | P | FAIL |
Troy Cobbley
|
|
|
We did not perform any actual testing today. I noted that the forward flush vavle was wired wrong, missing ceiling mounted horn/strobe, wrong batteries in the facp and four Bedrooms with the smoke detectors mounted less than 3'-0" from ceiling fans, PIV took 4 turns to activate tamper switch and the flow switch timing has not been verified.
|
Permit Ready to Issue | | | 11/30/2015 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/30/2015 | | DONE |
Christina Prado
|
|
|
|
(F) Reprint permit | | | 11/30/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/30/2015 | | 11/30/2015 | | DONE |
Christina Prado
|
|
|
|
1st review completed | | | 11/25/2015 | | FAIL |
|
|
|
Visual and audible notification for sleeping rooms does not meet current requirements of 2013 NFPA 72. Failed pre-screen review.
|
Miscellaneous action | | | 11/25/2015 | | DONE |
|
|
|
emailed applicant reason for failed pre-screen review.
|
Miscellaneous action | | | 11/25/2015 | | DONE |
|
|
|
Required design corrections uploaded.
|
Alarm Plan Check | 11/25/2015 | | 11/25/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 11/25/2015 | | DONE |
|
|
|
Plans approved with review comments.
|
Application received | | | 11/24/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Nov 24 2015 1:06PM
|
Plan assigned to (Lee) | 11/24/2015 | | 11/24/2015 | | DONE |
Lee G Meredith
|
|
|
|