INSP-Final Inspection | 6/1/2016 | 6/2/2016 | 6/2/2016 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Alarm Plan Check | 6/1/2016 | | 6/1/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 6/1/2016 | | DONE |
|
|
|
Plan modification approved. No new review comments.
|
Permit Ready to Issue | | | 6/1/2016 | | DONE |
|
|
|
plan mod only
|
CHANGE STATUS TO (ISS) | | | 6/1/2016 | | DONE |
|
|
|
plan mod fees paid
|
INSP-Final Inspection | 5/26/2016 | 5/26/2016 | 5/26/2016 | A | FAIL |
Troy Cobbley
|
|
|
Duct smoke detectors have been tested. To final this permit plan modifications will be required for the additional NAC panel and associated horn/strobes and then of course the testing of these devices.
|
Plan Modification Accepted | | | 5/26/2016 | | DONE |
|
|
|
Plan modification submitted to reflect numerous changes made during construction and to correct design errors found during acceptance inspections.
|
CHANGE STATUS TO (REV) | | | 5/26/2016 | | DONE |
|
|
|
|
INSP-Final Inspection | 5/24/2016 | 5/25/2016 | 5/25/2016 | P | FAIL |
Troy Cobbley
|
|
|
Head end equipment was verified. Interconnects with the fire sprinkler system were verified. I then did a walk through on the notification devices and noted several at the wrong candella and in one location nine new strobes will need to be added. Several locations have 15cd strobes mounted outside of their listing at 12"-0"
|
INSP-Final Inspection | 5/23/2016 | 5/24/2016 | 5/24/2016 | P | CANC |
Troy Cobbley
|
|
|
Phone #: 2089414511 >> Inspection requested via mobile web by Nathan Price
|
Issue and Print Permit | | | 12/31/2015 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/31/2015 | | 12/31/2015 | | DONE |
Brittany Hill
|
|
|
|
Plan resubmittals received | | | 12/30/2015 | | DONE |
|
|
|
|
Alarm Plan Check | 12/30/2015 | | 12/30/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 12/30/2015 | | DONE |
|
|
|
Resubmittal approved with review comments.
|
1st review completed | | | 12/18/2015 | | FAIL |
|
|
|
Failed due to inadequate visual notification. See 1st review comments.
|
Miscellaneous action | | | 12/18/2015 | | DONE |
|
|
|
Review comments emailed to Dante.
|
Application received | | | 12/17/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Dec 17 2015 10:59AM
|
Plan assigned to (Lee) | 12/17/2015 | | 12/17/2015 | | DONE |
Lee G Meredith
|
|
|
|