INSP-Final Inspection | 1/20/2016 | 1/21/2016 | 1/21/2016 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Permit Ready to Issue | | | 1/15/2016 | | DONE |
|
|
|
|
Telephone call | | | 1/15/2016 | | DONE |
|
|
|
called NW Security- told them permit is ready for pick up and fees due
|
Issue and Print Permit | | | 1/15/2016 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 1/13/2016 | | 1/14/2016 | | DONE |
Lee G Meredith
|
|
|
|
Plan resubmittals received | | | 1/14/2016 | | DONE |
|
|
|
Plan modification received.
|
Alarm Plan Check | 1/14/2016 | | 1/14/2016 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/14/2016 | | DONE |
|
|
|
Plan mod approved. No additional review comments.
|
CHANGE STATUS TO (REV) | | | 1/13/2016 | | DONE |
|
|
|
received two copies of sheet E2.1F, outdoor commander series evacuation signals, and signal circuit and voltage drop- put in fire cubby
|
INSP-Final Inspection | 1/5/2016 | 1/5/2016 | 1/5/2016 | P | FAIL |
Troy Cobbley
|
|
|
The audio and visual are not syncing as required. There are two distinct audible pulses at the west side of the building. I found two locations where there are atleast three visual flashes. Also the mens and womens showers and the old anecoic (sound) chamber have not been addressed for audio/visuals. The fire alarm contractor needs to address any and all deficiencies of the fire alarm system for this new occupancy.
|
Inspection Record Card- Fire | 1/4/2016 | | 1/4/2016 | | DONE |
Kristal Soland
|
|
|
|
Issue and Print Permit | | | 1/4/2016 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 12/21/2015 | | 12/31/2015 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/31/2015 | | DONE |
|
|
|
|
Alarm Plan Check | 12/31/2015 | | 12/31/2015 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 12/31/2015 | | DONE |
|
|
|
Plans approved with review comments.
|
Permit Ready to Issue | | | 12/31/2015 | | DONE |
|
|
|
NEED to add phone number, email info into FIRE company in the directory
|
Telephone call | | | 12/31/2015 | | DONE |
|
|
|
called David-let him know permit is ready for pick up and fees due
|
Telephone call | | | 12/30/2015 | | DONE |
|
|
|
Dave called to see if the plans were ready to pick up. I told him that they were failed on 12-21-15 and that I had called Tony to let him know corrections were required and the failed drawings were available at the front desk with correction notes. Resubmittals have not been received yet.
|
Application received | | | 12/21/2015 | | DONE |
|
|
|
Application submitted via PDS Online on Dec 21 2015 8:52AM
|
1st review completed | | | 12/21/2015 | | FAIL |
|
|
|
Strobe spacing is inadequate. Returned to applicant for corrections.
|
Telephone call | | | 12/21/2015 | | DONE |
|
|
|
Called Tony to let hime know that the strobe spacing is inadequate. He is to resubmit after corrections have been made.
Plans are in drawers behind permit techs
|