Permit Information
Permit NumberFIR15-00894
StatusFinaled
Name NORTHWEST SECURITY INC
Site Address 415 N MAPLE GROVE RD
Project NameEnviro-Tech
Customer Number 
ePlanReviewNo
Description
Horn/Strobe Relocate/Remove - modify notification device layout to accommodate a tenant improvement. Associated with building permit BLD15-03223.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/20/20161/21/20161/21/2016APASS
DetailsTroy Cobbley
Permit finaled
Permit Ready to Issue  1/15/2016 DONE
Telephone call  1/15/2016 DONE
called NW Security- told them permit is ready for pick up and fees due
Issue and Print Permit  1/15/2016 DONE
Plan assigned to (Lee)1/13/2016 1/14/2016 DONE
DetailsLee G Meredith
Plan resubmittals received  1/14/2016 DONE
Plan modification received.
Alarm Plan Check1/14/2016 1/14/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  1/14/2016 DONE
Plan mod approved. No additional review comments.
CHANGE STATUS TO (REV)  1/13/2016 DONE
received two copies of sheet E2.1F, outdoor commander series evacuation signals, and signal circuit and voltage drop- put in fire cubby
INSP-Final Inspection1/5/20161/5/20161/5/2016PFAIL
DetailsTroy Cobbley
The audio and visual are not syncing as required. There are two distinct audible pulses at the west side of the building. I found two locations where there are atleast three visual flashes. Also the mens and womens showers and the old anecoic (sound) chamber have not been addressed for audio/visuals. The fire alarm contractor needs to address any and all deficiencies of the fire alarm system for this new occupancy.
Inspection Record Card- Fire1/4/2016 1/4/2016 DONE
DetailsKristal Soland
Issue and Print Permit  1/4/2016 DONE
Plan assigned to (Lee)12/21/2015 12/31/2015 DONE
Details
Plan resubmittals received  12/31/2015 DONE
Alarm Plan Check12/31/2015 12/31/2015 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/31/2015 DONE
Plans approved with review comments.
Permit Ready to Issue  12/31/2015 DONE
NEED to add phone number, email info into FIRE company in the directory
Telephone call  12/31/2015 DONE
called David-let him know permit is ready for pick up and fees due
Telephone call  12/30/2015 DONE
Dave called to see if the plans were ready to pick up. I told him that they were failed on 12-21-15 and that I had called Tony to let him know corrections were required and the failed drawings were available at the front desk with correction notes. Resubmittals have not been received yet.
Application received  12/21/2015 DONE
Application submitted via PDS Online on Dec 21 2015 8:52AM
1st review completed  12/21/2015 FAIL
Strobe spacing is inadequate. Returned to applicant for corrections.
Telephone call  12/21/2015 DONE
Called Tony to let hime know that the strobe spacing is inadequate. He is to resubmit after corrections have been made.
Plans are in drawers behind permit techs