Information based on query as of Saturday, June 29, 2024.
Permit Information
Permit NumberFIR16-00017
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 7578 W SAXTON DR
Project NameKensington Apartments Bldg T
Customer Number 
ePlanReviewYes
Description
[Kensington Apartments - Building T]
The fire sprinkler scope of work consists of a NFPA 13R system for a four level apartment building. There floor level control valves in a valve house. The system is supplied by 2” underground through a 2” backflow preventer to 1 ½” riser. The system piping is 1” CPVC.

There are 2 manual 4” standpipes. The standpipes are a deferred submittal

Note: To achieve 500 Gpm @ 100 Psi a the top most standpipe outlets the fire apparatus is required to supply 505 Gpm @ 128 Psi

The underground for buildings T, O & P are under permit FIR15-00689
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/20/20169/23/20169/23/2016PPASS
DetailsJim Page
Final fire sprinkler inspection passed/complete, hydrostatic test was completed on 06MAY2016
INSP-Sprinkler Rough-in5/31/20165/31/20165/31/2016APART
DetailsJim Page
Tenting Inspection complete for overhead fire sprinkler piping in the 3rd level attic spaces as well as 4th level fire sprinkler piping, area's inspected approved for cover with exception to the breeze-ways, the piping crossing the breeze-way an all floors cannot be covered until an approved method is installed to keep this section of piping from freezing
INSP-Sprinkler Rough-in/Hydro5/5/20165/6/20165/6/2016APART
DetailsJim Page
Rough to cover inspection complete, 1st level overhead fire sprinkler piping approved for cover with exception to the fire sprinkler piping crossing the breeze-way, the piping crossing the breeze-way an all floors cannot be covered until an approved method is installed to keep this section of piping from freezing. 2nd level overhead fire sprinkler piping approved for cover with exception to breeze-way, 3rd level piping approved for cover will exception to breeze-way and piping that is located in attic space, the piping in th attic space needs to be tented with insulation, once tenting inspection is complete this piping can be covered, 4th level rough in inspection complete, all piping on 4th level cannot be covered until tenting inspection is complete. Any overhead fire sprinkler piping that is covered before tenting inspection will have covering material removed for the inspection.
INSP-Sprinkler Rough-in/Hydro5/5/20165/5/20165/5/2016PCANC
DetailsJim Page
Please call Jake when you are heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro4/25/20164/29/20164/28/2016PCANC
DetailsJim Page
Please call when you are headed out. Thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro4/20/20164/26/20164/25/2016PCANC
DetailsJim Page
Please call Jake when you are heading out. Thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
Miscellaneous action  4/14/2016 DONE
The FD is ok with dry standpipes but required
Locking KNOX FDC caps
One FDC connection for the standpipes and system.

I knew the code section was in NFPA 14 but since IFC overrules and it was not mention in IFC. Well I just wanted to make sure.

The IFC comment could always be made to happen. (Make them supply a heated chase and or heat tracing.) That is what I meant by huge expense.

It is going to be difficult to tie the FDC together. The regular FDC is at the side of the building. The SP FDC is in the middle. However, anything is possible. I will call them and see how much blow back I get.

In retrospect, I should have been more thorough on my question to you. Sorry.

Cordially,

Tim Frost, S.E.T.


Tim Frost, S.E.T.
Fire Sprinkler Plans Examiner
Planning & Development Services

Phone: ###-####
E-Mail: tfrost@cityofboise.org

150 North Capitol Boulevard
Boise, ID. 83701


From: Ronald Johnson
Sent: Wednesday, March 23, 2016 3:37 PM
To: Tim Frost
Subject: RE: Kensington

Tim,
First a couple code sections.

905.8 Dry standpipes. Dry standpipes shall not be installed.
Exception: Where subject to freezing and in accordance
with NFPA 14.

NFPA 14
5.4.1.1* Class I standpipe systems shall be permitted to be automatic
dry, automatic wet, semiautomatic dry, manual dry, or
manual wet in buildings not classified as high-rise buildings.

I just talked to Romeo about this to see how he’s handled it before. He hasn’t come across this exact scenario, nor have I. We are ok with the concept with the addition of a couple items.
1. Locking Knox caps on FDC’s.
2. Shared FDC with sprinklers to prevent us from having to supply an FDC and a standpipe connection.

Do you think that is doable?

Thanks,


Ron Johnson
Division Chief – Assistant Fire Marshal

###-#### -Office
###-#### -Cell

rjohnson@cityofboise.org

333 N. Mark Stall Place
Boise, ID 83704


From: Tim Frost
Sent: Wednesday, March 23, 2016 1:47 PM
To: Ronald Johnson
Subject: Kensington

We have talked several times about this project. However, just to make sure, you are ok with dry manual standpipes in these NPFA 13R apartment buildings; correct? They are not specifically referenced in IFC. The only reference for dry manual appears to be parking garages and basement. There really is any better way of doing them without a huge exspense.

905.3 Required Installations.
Standpipe systems shall be installed where required by Sections 905.3.1 through 905.3.8. Standpipe systems are allowed to be combined with automatic sprinkler
systems.
Exception: Standpipe systems are not required in Group R-3 occupancies.
905.3.1 Height.
Class III standpipe systems shall be installed throughout buildings where the floor level of the highest story is located more than 30 feet (9144 mm) above the
lowest level of the fire department vehicle access, or where the floor level of the lowest story is located more than 30 feet (9144 mm) below the highest level of
fire department vehicle access.
Exceptions:
1. Class I standpipes are allowed in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or
903.3.1.2.
2. Class I manual standpipes are allowed in open parking garages where the highest floor is located not more than 150 feet (45 720 mm) above the
lowest level of fire department vehicle access.
3. Class I manual dry standpipes are allowed in open parking garages that are subject to freezing temperatures, provided that the hose connections are
located as required for Class II standpipes in accordance with Section 905.5.
4. Class I standpipes are allowed in basements equipped throughout with an automatic sprinkler system.
5. In determining the lowest level of fire department vehicle access, it shall not be required to consider:
5.1. Recessed loading docks for four vehicles or less, and
5.2. Conditions where topography makes access from the fire
Sprinkler Plan Check4/12/2016 4/12/2016 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  4/12/2016 DONE
DetailsTim Frost
Permit Ready to Issue  4/12/2016 DONE
DetailsChristina Prado
CHANGE STATUS TO (ISS)  4/12/2016 DONE
DetailsChristina Prado
INSP-Sprinkler Rough-in/Hydro3/10/20163/10/20163/10/2016PPASS
DetailsJim Page
Underground rough to cover inspection complete, underground supply approved for cover. Hydrostatic test (200psi for 2 hours)for underground passed/complete.
Permit Ready to Issue  2/2/2016 DONE
Issue and Print Permit  2/2/2016 DONE
Inspection Record Card- Fire2/2/2016 2/2/2016 DONE
DetailsChristina Prado
Sprinkler Plan Check1/29/2016 1/29/2016 PASS
DetailsTim Frost
Please, see attached comments.
PLANS/APPL TAKEN TO FRONT DESK  1/29/2016 DONE
DetailsTim Frost
Sprinkler Plan Check1/15/2016 1/15/2016 FAIL
DetailsTim Frost
1st review completed  1/15/2016 FAIL
DetailsTim Frost
Miscellaneous action  1/15/2016 DONE
DetailsTim Frost
Emailed contractor in regards to failed review.
Intake Approval  1/14/2016 PASS
Plan assigned to (Tim)1/14/2016 1/14/2016 DONE
DetailsTim Frost
Application received  1/12/2016 DONE
Application submitted via PDS Online on Jan 12 2016 10:13AM