Permit Information
Permit NumberFIR16-00020
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 9543 W EMERALD ST
Project NameEmerald Bldg - Elev Addition
Customer Number 
ePlanReviewYes
Description
Add elevator recall and shunt to a new elevator in an existing building. Detectors have relay bases for recall and shunt interface. New devices will connect to existing/expanded DMP Fire Alarm panels. Project is associated with building permit BLD15-02730.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  6/6/2016 DONE
INSP-Final Inspection3/3/20163/3/20163/3/2016PPASS
DetailsJim Page
Final fire alarm inspection for elevator passed/complete.
INSP-Sprinkler Rough-in/Hydro3/2/20163/3/20163/3/2016PCANC
DetailsJim Page
Inspection request is for a fire alarm final, not a sprinkler rough-in/hydro, cancelling this inspection request and generating the correct request.
INSP-Final Inspection2/29/20163/2/20163/2/2016PFAIL
DetailsTroy Cobbley
Since the elevator contractor did not show up we could not get acces to the last heat detector to be tested in the elevator pit.
Plan Modification Accepted  2/26/2016 DONE
CHANGE STATUS TO (REV)  2/26/2016 DONE
Alarm Plan Check2/26/2016 2/26/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/26/2016 DONE
Plan modification approved. No additional review comments.
Permit Ready to Issue  2/26/2016 DONE
CHANGE STATUS TO (ISS)  2/26/2016 DONE
Miscellaneous action  2/24/2016 DONE
DAmie emailed as built drawings. I informed him that he need to upload them as a plan modification andd all files are to have the same name as previous.
Plan resubmittals received  2/24/2016 DONE
Changes to original plans.
INSP-Final Inspection2/19/20162/23/20162/23/2016PFAIL
DetailsTroy Cobbley
Provide plan modifications and correct recall function as discussed. Need to test heat detectors as well.
Telephone call  2/16/2016 DONE
Damie Lasater called to say that state elevator inspector Gary Barnes is requiring a heat detector at one lobby due to it being located outside. I agreed and told Damie that the heat detector would need to be rated for the environment.
Plan assigned to (Lee)1/14/2016 1/14/2016 DONE
DetailsLee G Meredith
1st review completed  1/14/2016 PASS
Alarm Plan Check1/14/2016 1/14/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  1/14/2016 DONE
Plans approved with review comments.
Permit Ready to Issue  1/14/2016 DONE
DetailsChristina Prado
Issue and Print Permit  1/14/2016 DONE
Inspection Record Card- Fire1/14/2016 1/14/2016 DONE
DetailsChristina Prado
Application received  1/13/2016 DONE
Application submitted via PDS Online on Jan 13 2016 12:09PM
Miscellaneous action  1/13/2016 DONE
Emailed a list of questions to Damie regarding detector listings and information missing on drawings. Damie addressed each question and sent an updated drawing that reflected the changes.