Permit NumberFIR16-00070
StatusFinaled
Name STATEFIRE DC SPECIALTIES
Site Address 1401 S ROBERT ST
Project NameWells Fargo Fin. Flr 2 FA
Customer Number 
ePlanReviewYes
Description
Replace the outdated fire alarm smoke detectors, pull stations, and duct detector on the second floor and first floor main entry. Also add full horn/strobe notification in remodeled areas in order to bring those areas up to code. Work will take place during the second floor remodel and first floor main entry remodel.
Building currently has full smoke detection and pull stations at each exit. Associated with byulding permit BLD15-04361.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Fees Due Hold6/22/2016 8/18/2016 DONE
Details
sent statement on 8-1-16 for fees due
Print Statement  8/3/2016 DONE
INSP-Final Inspection6/21/20166/22/20166/22/2016APASS
DetailsJim Page
Previously noted items have been addressed/repaired. Final fire alarm inspection passed/complete
Permit Ready to Issue  6/21/2016 DONE
plan mod fees due - DO NOT re-issue
CHANGE STATUS TO (ISS)  6/21/2016 DONE
DetailsChristina Prado
Plan Modification Accepted  6/21/2016 DONE
CHANGE STATUS TO (REV)  6/21/2016 DONE
Plan modification received.
Alarm Plan Check6/21/2016 6/21/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/21/2016 DONE
Plan modification approved with review comments.
INSP-Final Inspection6/14/20166/16/20166/16/2016AFAIL
DetailsTroy Cobbley
Resubmit plans showing the three peaked sky lights with additional protection and show the two ceiling levels that surround the sky lights, show candella changes on the second floor, provide sync for all notification devices, provide additional notification in the basement lobby, provide the sample tubes and remote annunciators for the duct smoke detectors. The only devices tested today was the first floor lobby manual pull station, four fire/smoke damperson the first floor and the south duct detector on the second floor. All other devices need to be tested. I noted that the first floor manual pull station activated elevator recall which is not allowed in current code.
INSP-Final Inspection6/14/20166/15/20166/14/2016ACANC
DetailsJim Page
If you cannot reach me, please call Kenny Leslie @ ###-####
or Mike Kroll @ ###-#### Phone #: ###-#### >> Inspection requested via web by Josiah Monett Inspection cancelled from web by: Josiah Monett
Plan Modification Accepted  6/14/2016 DONE
Plan mod includes added duct smoke detectors, fire smoke dampers and notification in specific areas. Added notification augments existing notification.
Alarm Plan Check6/14/2016 6/14/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  6/14/2016 DONE
Plan mod approved with updated review comments.
CHANGE STATUS TO (ISS)  6/14/2016 DONE
(F) Reprint permit  6/14/2016 DONE
Miscellaneous action  6/10/2016 DONE
Kenny requested the project be opened for a plan modification to include phase 3 work.
CHANGE STATUS TO (REV)  6/10/2016 DONE
Project reopened for phase 3 plan modification.
Alarm Plan Check2/8/2016 2/8/2016 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  2/8/2016 DONE
Plans approved with review comments.
Permit Ready to Issue  2/8/2016 DONE
Issue and Print Permit  2/8/2016 DONE
Inspection Record Card- Fire2/8/2016 2/8/2016 DONE
DetailsChristina Prado
1st review completed  2/5/2016 FAIL
See 1st review comments.
Plan assigned to (Lee)2/4/2016 2/4/2016 DONE
DetailsLee G Meredith
Miscellaneous action  2/4/2016 DONE
Drawing uploaded incorrectly. I emailed Kenny and requested corrections.
Application received  2/2/2016 DONE
Application submitted via PDS Online on Feb 2 2016 4:04PM