INSP-Final Inspection | 7/8/2016 | 7/11/2016 | 7/11/2016 | A | PASS |
Jim Page
|
|
|
Previously noted items addressed/repaired, final fire sprinkler inspection passed/complete.
|
INSP-Final Inspection | 7/5/2016 | 7/5/2016 | 7/5/2016 | P | FAIL |
Troy Cobbley
|
|
|
Provide inspectors test/drain as per approved plans, riser in garage closet needs to be installed with-in 1 1/2" of wall or needs to be steel, most of the piping in the basement does not meet the installation requirements for exposed piping in unfinished basements per the Spears Manual.
|
INSP-Sprinkler Rough-in | 2/29/2016 | 2/29/2016 | 2/29/2016 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection completed, including tenting for fire sprinkler piping located in attic space, complete area of work approved for cover.
|
Sprinkler Plan Check | 2/22/2016 | | 2/22/2016 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/22/2016 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 2/22/2016 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/22/2016 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/22/2016 | | 2/22/2016 | | DONE |
Christina Prado
|
|
|
|
Intake Approval | | | 2/12/2016 | | PASS |
|
|
|
|
Plan assigned to (Tim) | 2/12/2016 | | 2/12/2016 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 2/12/2016 | | 2/12/2016 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 2/12/2016 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 2/12/2016 | | DONE |
Tim Frost
|
|
|
Emailed contractor in regards to failed review.
|
Application received | | | 2/5/2016 | | DONE |
|
|
|
Application submitted via PDS Online on Feb 5 2016 1:44PM
|